RIBMNWLB-7-BC
Details
Details
RIBMNWLB-7-BC AHU Fan Safety Alarm and Logic Circuit, BACnet MS/TP, 7 Binary Inputs, 2 Binary Outputs, Track Mount (2.75 in.)
Open circuit board for air handler safety wiring: in its default mode, BO 1 closes only while all six alarm inputs (BI 1-BI 6) are closed, and BO 2 follows BI 7. Inputs have override and latching DIP switches with a clear-latches pushbutton. It can also be set up as a plain I/O board.
Key Features
- Logic: Fan Safety Circuit mode by default: BO 1 closes when BI 1-BI 6 are all closed; BO 2 follows BI 7. Can also run as an I/O board with 2 BO and 7 BI
- Inputs/Outputs: 2 BO (relays) with override; 7 BI; BI 1-BI 6 with override and latching DIP switches
- Power input: 24 VAC/DC, 50-60 Hz; 75 mA @ 24 VAC or 30 mA @ 24 VDC, plus the BO 1-1 load
Product Specifications
| Manufacturer | Functional Devices |
|---|---|
| Model | RIBMNWLB-7-BC |
| Type | AHU fan safety alarm and general purpose logic circuit, BACnet MS/TP, track mount (circuit board) |
| Network | BACnet MS/TP; twisted pair 22-24 AWG, shielded recommended; 9600 to 115200 baud; address and baud rate set by DIP switches |
| Inputs/Outputs | 2 BO (relays) with override; 7 BI; BI 1-BI 6 with override and latching DIP switches |
| Logic | Fan Safety Circuit mode by default: BO 1 closes when BI 1-BI 6 are all closed; BO 2 follows BI 7. Can also run as an I/O board with 2 BO and 7 BI |
| Contact ratings | BO 1-1: 3A max @ 24 VAC or 24 VDC; BO 1-2: 10A resistive @ 30 VDC, 10A general use @ 277 VAC; BO 2: 20A resistive @ 277 VAC, 20A ballast @ 277 VAC |
| Power input | 24 VAC/DC, 50-60 Hz; 75 mA @ 24 VAC or 30 mA @ 24 VDC, plus the BO 1-1 load |
| Override | Relay override by DIP switch |
| Dimensions | 6.62 in. H x 2.75 in. W x 1.25 in. D1 / 1.75 in. D2 |
| Mounting | 2.75 in. track |
| Operating temperature | -30 to 140 deg F |
| Siblings | RIBTWLB-7-BC: NEMA 1 housing |