RIB12S-FA-NC
Details
Details
RIB12S-FA-NC Polarized Fire Alarm Relay, 10A SPST-NC with Override, 12 VAC/DC Coil
Relay with a polarized coil, doubled coil leads and a single-throw normally closed contact. A closed/open/auto switch forces the contact by hand. NEMA 1 gray housing accepted for use in plenum, with UL864 and California State Fire Marshal approvals. Mounts on a 0.50 in. NPT hub.
Key Features
- Override: Override switch: closed, open, auto
- Coil voltage: 12 VAC/DC, polarized
- Contact ratings: 10A general use @ 277 VAC; 10A resistive @ 30 VDC (NO)
Product Specifications
| Manufacturer | Functional Devices |
|---|---|
| Model | RIB12S-FA-NC |
| Type | Enclosed polarized fire alarm relay |
| Contacts | One SPST-NC, continuous duty coil |
| Contact ratings | 10A general use @ 277 VAC; 10A resistive @ 30 VDC (N/O); 7A resistive @ 30 VDC (N/C); 1 HP @ 250 VAC |
| Coil voltage | 12 VAC/DC, polarized (Wht/Blu +, Wht/Yel -); 50-60 Hz |
| Override | Override switch: closed, open, auto |
| Housing | NEMA 1, gray, accepted for use in plenum |
| Dimensions | 1.70 in. H x 2.80 in. W x 1.50 in. D, with 0.50 in. NPT hub |
| Mounting | 0.50 in. NPT hub |
| Wires | 16 in. leads, 600 V rated |
| Operating temperature | -30 to 140 deg F |
| Approvals | UL Listed, UL916, UL864, C-UL, CE, RoHS, California State Fire Marshal |
| Siblings | RIB12C-FA: SPDT; RIB12C-FA-RD: SPDT, red housing; RIB12C-FA-N4: SPDT, NEMA 4/4X housing; RIB12S-FA: SPST-N/O with override; RIB12S-FA-RD: SPST-N/O with override, red housing; RIB24S-FA-NC: 24 VAC/DC coil |