Prolon PL-C1050-WLC Water Loop Controller, 4 In / 5 Out
Controls a boiler and a cooling tower with an internal pump on a water loop, from supply water temp.
Key Features
- Up to 2 cooling tower stages, 1 modulating
- Bypass valve on return temp
- Tower damper sequence
- Modbus RTU
Product Specifications
| Manufacturer | Prolon |
|---|---|
| Model | PL-C1050-WLC |
| Application | Water loop: boiler plus cooling tower with internal pump |
| Inputs | Supply water, return water, auxiliary temp: 10k thermistor; auxiliary: dry contact |
| Digital outputs | 4 triac, 10-30 VAC source or dry contact, 300 mA max (resettable fuse) |
| Analog output | 1 x 0-10 VDC, 40 mA max (resettable fuse) |
| Sequences | Boiler and tower control on supply temp, bypass valve on return temp, up to 2 tower stages (1 modulating), tower damper |
| Supply | 24 VAC +/-10%, 50/60 Hz, Class 2 |
| Power | 2 VA consumption, 32 VA input |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Indication | LEDs for each output, communication, power and microprocessor state |
| Microprocessor | PIC18F6722, 8-bit, 40 MHz, 128 KB flash |
| Connection | Removable screw terminal blocks, 16 AWG max |
| Casing | Molded ABS, UL94-HB |
| Dimensions | 6.2 x 5.2 x 2.5 in. (157 x 132 x 64 mm) |
| Weight | 0.85 lb (0.39 kg) |
| Environment | -4 to 122 deg F (-20 to 50 deg C), non-condensing |
| Certification | UL916, CAN/CSA-C22.2, RoHS, FCC Part 15 Class B |