BAC-190063CW
Details
Details
BAC-190063CW FlexStat Touchscreen Controller for Fan Coil, Heat Pump and Rooftop Units, Temperature Only, BACnet MS/TP
Wall-mounted touchscreen controller with a built-in temperature sensor, set up to run a fan coil unit, heat pump, or rooftop unit. It configures from the screen out of an on-board library. Six more inputs take external sensors, and the unit is fully programmable with KMC software.
Key Features
- Outputs: 6 relays (NO SPST, 1 A each, 1.5 A per bank of 3 at 24 VAC/DC); 3 universal (0-12 VDC, up to 100 mA each, 100 mA total per bank of 3)
- Inputs: 6 universal: 1k and 10k ohm sensors, 0-12 VDC or 0-20 mA
- Network: BACnet MS/TP, 9.6 to 115.2 kbaud
Product Specifications
| Manufacturer | KMC Controls |
|---|---|
| Model | BAC-190063CW |
| Type | Touchscreen BACnet room controller with built-in sensors |
| Application | Fan coil units (2- and 4-pipe), heat pump units, and rooftop units |
| Built-in sensors | Temperature only |
| Temperature sensor | Thermistor, 10k Type II, +/-0.36 deg F |
| Inputs | 6 universal: 1k and 10k ohm sensors, 0-12 VDC or 0-20 mA |
| Outputs | 6 relays (NO SPST, 1 A each, 1.5 A per bank of 3 at 24 VAC/VDC); 3 universal (0-12 VDC, up to 100 mA each, 100 mA total per bank of 3) |
| Network | BACnet MS/TP, 9.6 to 115.2 kbaud, screw terminals; EIA-485 data port on the underside of the case for temporary access |
| BACnet profile | Advanced Application Controller (B-AAC) |
| Programming | On-board program library set from the touchscreen; custom Control Basic with KMC software |
| Clock | Real time clock with 72-hour capacitor backup |
| Display | Color resistive touchscreen |
| Supply voltage | 24 VAC (50/60 Hz) or 24 VDC (-15%, +20%), Class 2; 13 VA plus external loads |
| Mounting | Flat surface, 2 x 4 in. box, or 4 x 4 in. box with HMO-10000W |
| Dimensions | 3-7/8 x 5-1/8 x 1-5/16 in. |
| Operating limits | 34 to 125 deg F (1.1 to 51.6 deg C), 0 to 95% RH non-condensing |
| Approvals | UL 916; FCC Class A |
| Warranty | 5 years from date code |
| Note | Not a plug-in replacement for BAC-1000/120000/130000/140000 FlexStats; the new backplate must be installed |
| Siblings | BAC-190063CEW: BACnet IP; BAC-190036CW: AHU and unit ventilator models (3 relays, 6 outputs); BAC-190263CW: temp/RH; BAC-192063CW: temp/motion; BAC-192263CW: temp/RH/motion; BAC-193263CW: temp/RH/CO2; BAC-195263CW: temp/RH/CO2/motion |