171A-10303 1/2 in. 2-Way Ball Valve with GDE131.1P Non-Spring Return Actuator, Floating, 24 VAC

Holds its last position on power loss (fail-in-place).

Runs on AC power only; no DC rating.

Has no position feedback or auxiliary switches.

Handles hot or chilled water up to 50% glycol, 0 to 250 deg F; not for steam.

Limits operating differential pressure to 60 psi.

Key Features

  • Cv: 1.6
  • Close-off: 200 psi
  • Ball: chrome-plated brass; stem: brass
  • Flow characteristic: equal percentage
  • Torque: 44 lb-in

Product Specifications

ManufacturerSiemens
Model171A10303 (171A-10303)
Product599 Series 2-way ball valve + OpenAir GDE131.1P non-spring return actuator assembly
Valve body part number599-10303
Fail actionFail-in-place (non-spring return); holds position on power failure
Line size1/2 in (15 mm)
Cv (Kvs)1.6 (1.4)
PortCharacterized (flow characterizer insert)
Ball materialChrome-plated brass
Stem materialBrass
Body materialBrass: ASTM B283, C37700
Ball sealsGlass filled PTFE with EPDM O-rings
Flow characterizer materialGlass filled PTFE
End connectionsInternal NPT
Stem sealsEPDM O-rings
Stem designBlow-out proof stem withstands high pressure
Valve body ratingANSI 250/600 WOG
Controlled mediumWater, water-glycol solutions to 50%
Angle of rotation0 to 90 deg
Flow characteristicEqual percentage (characterized bodies; parabolic flow characterizer orifice)
Canadian Registration Number (CRN)OC8213.5ADD4
Mounting locationNEMA 1 (interior only); NEMA 3R (with weather shield)
Mounting plateUniversal mounting plate; actuator and plate can be rotated in 90-degree increments (any of four rotation angles relative to the valve body)
Thermal barrierStandoffs provide a thermal barrier between the actuator and the mounting plate
Manual operationOperating handle for manual operation
OrientationBest performance with actuator above the valve body; in a horizontal pipe, any position between vertical and 90 deg; may also be installed vertically; do not install with the actuator below horizontal or upside-down
Service envelope2-1/2 in (60 mm); 8 in (200 mm) above; 1 in (25 mm) at sides; 4 in (100 mm) at end
Assembly wiringWhen ordered as an assembly, the actuator is provided with 3-foot (.9 m) wires
Close-off rating200 psi (1379 kPa), ANSI Class IV
Maximum operating differential pressure60 psi (414 kPa)
Media temperature0 deg F to 250 deg F (-18 deg C to 121 deg C)
Dimension A (Length)2-7/16 (61) in
Dimension B (Height)2-1/4 (57) in
Dimension C (C Length, GDE (171A-D))5-1/4 (133) in
Dimension C (C Length, GQD (171H, J, K, L, N))5-1/4 (133) in
Dimension D (Width)2-3/4 (70) in
Dimension E (Height)4-13/16 (123) in
Valve and bracket weight1 lb (0.45 kg)
Assembly wiringActuator ships with 3 ft (0.9 m) wires when ordered as an assembly
ActuatorGDE131.1P, non-spring return (fail-in-place), floating, 24 VAC
Actuator typeOpenAir non-spring return, direct-coupled rotary electronic actuator, 24 VAC floating control
Operating voltage (G-Y1 or G-Y2)24 VAC +20%, -15%
Actuator frequency50/60 Hz
Power consumption2.3 VA
Actuator equipment ratingClass 2 according to UL, CSA; Class III per EN60730
Control signalFloating (tri-state): 24 VAC on wires 1 and 6 (G-Y1) rotates clockwise; 24 VAC on wires 1 and 7 (G-Y2) rotates counterclockwise; angle of rotation is proportional to how long the signal is applied
Wiring (pre-cabled leads)1 = Supply G (red); 6 = Y1 control signal clockwise (violet); 7 = Y2 control signal counterclockwise (orange)
Direction of rotationReversed by interchanging wires 6 and 7 (Y1 and Y2) at the controller
Position feedbackNone (feedback potentiometer only on GDE132.1P; cannot be added in the field)
Auxiliary switchesNone (dual auxiliary switches only on GDE136.1P; cannot be added in the field)
Actuator torque44 lb-in (5 Nm)
Running time (90 deg opening or closing)90 sec at 60 Hz (108 sec at 50 Hz)
Nominal angle of rotation90 deg
Maximum angular rotation95 deg
Action on power failureHolds position on power failure or with no control voltage (non-spring return, fail-in-place)
Actuator manual overrideYes - red slide knob; move and lock position with no power present; returns to automatic control when power is restored
Mechanical range adjustmentAdjustable mechanical range stop (set screw, 4 mm hex)
Actuator enclosureNEMA Type 2; IP54 according to EN 60529
Outdoor ratingNEMA Type 4X (UL listed) only when installed with ASK75.7U weather shield and outdoor-rated conduit fittings
Actuator housing materialDurable plastic
Actuator gear lubricationSilicone-free
Ambient temperature, operation-25 deg F to 130 deg F (-32 deg C to 55 deg C)
Ambient temperature, storage and transport-40 deg F to 158 deg F (-40 deg C to 70 deg C)
Ambient humidity95% rh (non-condensing)
Agency certificationUL listed to UL873; cUL certified to Canadian Standard C22.2 No. 24-93; CE certified
Plenum approvalApproved for installation in plenum areas by UL per UL 1995
EMC conformity (plenum models)EMC directive 2004/108/EC; emissions EN61000-6-3; immunity EN61000-6-2
Actuator connectionPre-cabled, 18 AWG
Standard cable length3 ft (0.9 m)
Actuator life cycleDesigned for over 60,000 full strokes and a minimum of 1.5 million repositions at rated torque and temperature
Actuator dimensions6.2 in L x 2.8 in W x 2.4 in D (157 mm L x 71 mm W x 61 mm D)
Actuator weight1.06 lb (0.48 kg)
Transformer requirementsEarth-ground isolating step-down Class 2 transformer; no autotransformers; total VA of all loads must not exceed transformer rating; recommended max 10 actuators per transformer
Controller time-outUse a controller/software time-out that removes the drive signal after a predefined time to prolong actuator life