131F0668

SKU: 131F0668
$1,340.87

Call for Availability - (510) 636-7900

Details

Details

FC 102 VFD, 5 HP (4 kW), 3-Phase 380-480 VAC, NEMA 1 (IP21)

Drive only: no disconnect, fuses, or bypass.

Needs 3-phase input power.

BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN are built in; no option cards are installed.

Size it so the continuous output current meets the motor full-load amps.

Key Features

  • Output current: 10 A at 380-440 VAC, 8.2 A at 441-480 VAC (continuous)
  • RFI filter: built in

Product Specifications

ManufacturerDanfoss
Model131F0668
ProductVLT HVAC Drive FC 102
Type codeFC-102P4K0T4E21H2XGXXXXSXXXXAXBXCXXXXDX
Power rating4 kW / 5 HP at 460 VAC
Overload ratingNormal overload, 110% for 1 minute
Supply voltage3-phase 380-480 VAC (+/-10%)
Supply frequency50/60 Hz
Output current, continuous (380-440 VAC)10 A
Output current, continuous (441-480 VAC)8.2 A
Output current, intermittent (380-440 VAC)11 A
Output current, intermittent (441-480 VAC)9.0 A
Output power, continuous (400 VAC)6.9 kVA
Output power, continuous (460 VAC)6.5 kVA
Output voltage0-100% of supply voltage
Output frequency0-590 Hz
Power loss at rated load124 W
Efficiency0.97
SCCR100 kA rms
EnclosureIP21 / UL Type 1
Frame sizeA2
Mains optionNone
RFI filterYes
DC link reactorBuilt in
Brake chopperNone
KeypadGraphical local control panel (LCP 102)
Coated circuit boardsNo
Cable entriesStandard
Option cards (slots A, B, C, D)None installed
Built-in protocolsFC Protocol, BACnet MS/TP, Modbus RTU, Metasys N2, Apogee FLN
Digital inputs6 programmable (2 can be used as digital outputs), PNP or NPN, 0-24 VDC
Analog inputs2, 0-10 V or 0/4-20 mA (scalable)
Analog output1, 0/4-20 mA
Relay outputs2 programmable (240 VAC, 2 A and 400 VAC, 2 A)
Ramp times1-3600 s
Dimensions (H x W x D)14.8 x 3.5 x 8.1 in.
Net weight10.7 lb
Shipping weight12.5 lb