131B9874
Details
Details
FC 102 VFD, 40 HP (30 kW), 3-Phase 200-240 VAC, NEMA 12 (IP55)
Drive only: no disconnect, fuses, or bypass.
Needs 3-phase input power.
BACnet MS/TP, Modbus RTU, Metasys N2, and Apogee FLN are built in; no option cards are installed.
Size it so the continuous output current meets the motor full-load amps.
Key Features
- Output current: 115 A at 200-240 VAC (continuous)
- RFI filter: built in
Product Specifications
| Manufacturer | Danfoss |
|---|---|
| Model | 131B9874 |
| Product | VLT HVAC Drive FC 102 |
| Type code | FC-102P30KT2P55H2XGXXXXSXXXXAXBXCXXXXDX |
| Power rating | 30 kW / 40 HP at 208 VAC |
| Overload rating | Normal overload, 110% for 1 minute |
| Supply voltage | 3-phase 200-240 VAC (+/-10%) |
| Supply frequency | 50/60 Hz |
| Output current, continuous (200-240 VAC) | 115 A |
| Output current, intermittent (200-240 VAC) | 127 A |
| Output power, continuous (208 VAC) | 41.4 kVA |
| Output voltage | 0-100% of supply voltage |
| Output frequency | 0-590 Hz |
| Power loss at rated load | 1140 W |
| Efficiency | 0.97 |
| SCCR | 100 kA rms |
| Enclosure | IP55 / UL Type 12, with backplate |
| Frame size | C1 |
| Mains option | None |
| RFI filter | Yes |
| DC link reactor | Built in |
| Brake chopper | None |
| Keypad | Graphical local control panel (LCP 102) |
| Coated circuit boards | No |
| Cable entries | Standard |
| Option cards (slots A, B, C, D) | None installed |
| Built-in protocols | FC Protocol, BACnet MS/TP, Modbus RTU, Metasys N2, Apogee FLN |
| Digital inputs | 6 programmable (2 can be used as digital outputs), PNP or NPN, 0-24 VDC |
| Analog inputs | 2, 0-10 V or 0/4-20 mA (scalable) |
| Analog output | 1, 0/4-20 mA |
| Relay outputs | 2 programmable (240 VAC, 2 A and 400 VAC, 2 A) |
| Ramp times | 1-3600 s |
| Dimensions (H x W x D) | 27 x 12.1 x 12.2 in. |
| Net weight | 88 lb |
| Shipping weight | 94.6 lb |