UN-RL1644MS24NMC

SKU: UNRL1644MS24NMC

This item is IN STOCK

Current Stock: 20

Details

Details

Controlco Product Information Tabs
Product DetailsSpecificationsDownloads

Product Information


Optimizer Unitary Controller, 16UIO,4SSR,4Rel,MSTP,Sylk,24VA/VD


Honeywell Unitary Controllers provide flexible, freely programmable, demand-led control that delivers tangible benefits to reduce energy spending while driving new levels of functionality and efficiency in today’s buildings.


Features and Highlights


• UIOs configurable as analog input, binary input, and analog output
• Sylk™ two-wire polarity insensitive interface connects to Honeywell Sylk™ wall modules without hardware I/O.
• Engineering tools including function block library and sample application templates ensuring a consistent experience from the room, plant controllers, and supervisor.
• Easy to install into fusebox (DIN43880) or on DIN rail, surface mount
• Honeywell T1L devices support daisy chains with distances between devices of up to 984 ft. (300 m), way above the 328 ft. (100 m) limit of standard RJ45 ethernet and allowing greater wiring lengths.
Integrated Actuator Specifications

Specifications


Hardware


ParameterSpecification
CPUCrossover processor NXP I.MRT, Cortex M7
Memory capacity16 MB QSPI Flash, 16 MB SDRAM
EthernetBACnet™ IP: 2 × RJ‑45 Ethernet ports with loop topology protection (RSTP supported).
Real Time Clock24 hours backup after power failure; resets to factory default after 24h until BACnet™ Time Sync.
Small LEDsCommunication signal (green).
Large LEDsController status (green, yellow, red).


Electrical


ParameterSpecification
Rated Input Voltage20–30 VAC / 24–30 VDC
Nominal Power ConsumptionBACnet™ IP/MS/TP/T1L: 8 VA
Full Load Power ConsumptionBACnet™ IP/MS/TP/T1L: 30 VA
Frequency Range50–60 Hz
Auxiliary Power OutputLarge: 1 × 24 VAC/VDC @ 300 mA; 3 × 24 VAC/VDC @ 75 mA. Small: 1 × 24 VAC/VDC @ 300 mA; 1 × 24 VAC/VDC @ 75 mA.
Impulse Voltage330 VAC


Operational Environment


ParameterSpecification
Storage Temperature−40 °F to 150 °F (−40 °C to 66 °C)
Operating Temperature−40 °F to 122 °F (−40 °C to 50 °C)
Humidity5–95% RH, non‑condensing
ProtectionIP20, NEMA 1
Pollution Level2


Supported Devices


Device TypeModels
Sylk™ wall modulesTR42, TR42‑H, TR42‑CO2, TR71, TR75, TR120 (emulation mode only), etc.
Sylk™ sensorsTR40, TR40‑H, TR40‑CO2, TR50 (emulation mode only), C7400S
Sylk™ actuatorsMS3103, MS3105, MS3110, MS3120
Non-Sylk™ actuatorsMS4103, MS4105, MS7403, MS7503, MS8103, MS8105
Hardwired wall modulesT7460 A–F, T7770 A–G
Modbus devicesAny Modbus RTU devices, including Honeywell DALI64MODPSUF/S, TR50, TR80


Solid State Relay (SSR)


Max 24 VAC/VDC. 1.5 A constant; 3.5 A inrush for 0.1s per SSR output. Shared jumper supply. Fuse 5 A (examples: 0AGC005.V, BK/AGW-5).


Relays


Up to 277 VAC / 230 VAC (+20%). 3 contacts per relay (NO, NC, common). 10 A constant on NO, 100 A inrush for 100 ms. Total current limited to 12 A. Fuse 12.5 A (examples: 021812.5MXEP). Outputs usable as dry contact.


Universal IO


ParameterSpecification
AI16-bit A/D; 0–10 VDC or 0–20 mA; supports multiple sensor types and wall modules.
BIDry contact input; pulse input up to 100 Hz; compatible with SO interface.
AOVoltage output 0–11 VDC; current output 0–20 mA; LED control.
DO0/10 VDC at 20 mA binary output.


Communication


ParameterSpecification
ProtocolsBACnet™ IP (RJ45, T1L), BACnet™ MS/TP, Modbus RTU
IP AddressingDynamic: DHCP, Link-local; Static: Assigned
Sylk™2-wire, polarity-insensitive
Note *** Auto baud detection for BACnet™ MS/TP controllers


T1L Communication


ParameterSpecification
10BASE‑T1L Standard802.3cg‑2019
ConnectionScrew terminal, auto MDI‑X
Cable typeSingle twisted pair, 18 AWG, shielded or unshielded. Belden 74040NH, 9841NH or equivalent.
DistanceMax 984 ft (300 m) to Honeywell T1L controller in daisy chain; max 2,952 ft (900 m) to other T1L device without daisy chain.
Transmission rate10 Mbps