TGW-BCX-AW
Details
Details
Senva TGW-BCX-AW Wall CO Gas Detector, BACnet/Modbus, White Solid Lid
Detects CO and reports it over RS-485 as BACnet MS/TP, Modbus RTU, or Modbus ASCII; has no analog outputs. Switches a fan relay and an alarm relay at adjustable CO setpoints and sounds an 85 dB alarm, so it also works as a stand-alone controller. Mounts 3 to 6 ft above the floor. Needs an isolated Class 2 supply; the relays do not switch mains voltage.
Key Features
- CO Sensor Life: >7 years
- CO Fan Relay Setpoint: 25 ppm default (0-1000 ppm menu selectable)
- Replacement CO Element: TGS-CO-ULV2
Product Specifications
| Manufacturer | Senva |
|---|---|
| Model | TGW-BCX-AW |
| Gases | Carbon monoxide (CO) |
| Output Type | BACnet/Modbus (RS-485) |
| Temperature Sensor | None |
| Lid | White/solid lid |
| Power Supply | 15-30 VDC or 24 VAC, 4 W max., 160mA max.; Class 2 LPS or greater isolated supply; no mains connection |
| Wiring | 14-24 AWG, minimum 600V, 75 deg C |
| Terminal Torque | 4.4 lb-in (0.5 N-m) |
| Communications | RS-485: BACnet MS/TP, Modbus RTU, or Modbus ASCII |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| RS-485 Loading | 1/4 unit load |
| CO Sensor Type | Electrochemical |
| CO Accuracy | +/-5% of default range; +/-5% of reading above 200 ppm (full scale 1000 ppm) |
| CO Resolution | 1 ppm |
| CO Sensor Certification | UL2075 Recognized Component |
| CO Sensor Life | >7 years |
| CO Recommended Calibration | Annual |
| CO Mounting Height and Coverage | 3 to 6 ft; 5000-7500 sq ft |
| CO Fan Relay Setpoint | 25 ppm default (0-1000 ppm menu selectable) |
| CO Alarm Relay Setpoint | 100 ppm default (0-1000 ppm menu selectable) |
| Replacement CO Element | TGS-CO-ULV2 |
| Fan Relay (standard version) | NC, 1A @ 24/30 VDC (50/60 Hz), no mains connection |
| Alarm Relay (standard version) | NC, 1A @ 24/30 VDC (50/60 Hz), no mains connection |
| Display | 3-1/2 digit LCD |
| LEDs | Green = normal, yellow = warning/fan relay, red = alarm/alarm relay |
| Audible Alarm | 85 dB piezo; 30 minutes above alarm setpoint per UL2075 (menu selectable) |
| Calibration | Sensors NIST pre-calibrated with certificate of calibration; field replaceable |
| Operating Environment | -4 to 122 deg F (-20 to 50 deg C); 15-95% RH continuous, 0-95% intermittent; max. elevation 6,562 ft (2000 m) |
| Mounting | Wall |
| Enclosure Material | ABS/polycarbonate |
| Dimensions | 4.0 x 4.4 x 2.1 in. (H x W x D) |
| Conduit Opening | Tapped 1/2 in. NPT |
| Enclosure Rating | IP43 or NEMA 3R |
| Compliance | UL61010-1 listed; UL, cUL, CE |