TGW-ACX-A

SKU: TGWACXA
$495.65

Call for Availability - (510) 636-7900

Details

Details

Senva TGW-ACX-A Wall CO Gas Detector, Analog Outputs

Detects CO and outputs it on two programmable analog outputs (0-10V default, 0-5V, 1-5V, or 4-20mA). Switches a fan relay and an alarm relay at adjustable CO setpoints and sounds an 85 dB alarm, so it also works as a stand-alone controller. Mounts 3 to 6 ft above the floor. Needs an isolated Class 2 supply; the relays do not switch mains voltage.

Key Features

  • CO Sensor Life: >7 years
  • CO Fan Relay Setpoint: 25 ppm default (0-1000 ppm menu selectable)
  • Replacement CO Element: TGS-CO-ULV2

Product Specifications

ManufacturerSenva
ModelTGW-ACX-A
GasesCarbon monoxide (CO)
Output TypeAnalog
Temperature SensorNone
LidStandard
Power Supply15-30 VDC or 24 VAC, 4 W max., 160mA max.; Class 2 LPS or greater isolated supply; no mains connection
Wiring14-24 AWG, minimum 600V, 75 deg C
Terminal Torque4.4 lb-in (0.5 N-m)
Analog Outputs2 programmable outputs: 0-10V (default), 0-5V, 1-5V, or 4-20mA (menu selectable)
CO Output Scaling0-200 ppm (default) or 0-1000 ppm (menu selectable)
CO Sensor TypeElectrochemical
CO Accuracy+/-5% of default range; +/-5% of reading above 200 ppm (full scale 1000 ppm)
CO Resolution1 ppm
CO Sensor CertificationUL2075 Recognized Component
CO Sensor Life>7 years
CO Recommended CalibrationAnnual
CO Mounting Height and Coverage3 to 6 ft; 5000-7500 sq ft
CO Fan Relay Setpoint25 ppm default (0-1000 ppm menu selectable)
CO Alarm Relay Setpoint100 ppm default (0-1000 ppm menu selectable)
Replacement CO ElementTGS-CO-ULV2
Fan Relay (standard version)NC, 1A @ 24/30 VDC (50/60 Hz), no mains connection
Alarm Relay (standard version)NC, 1A @ 24/30 VDC (50/60 Hz), no mains connection
Display3-1/2 digit LCD
LEDsGreen = normal, yellow = warning/fan relay, red = alarm/alarm relay
Audible Alarm85 dB piezo; 30 minutes above alarm setpoint per UL2075 (menu selectable)
CalibrationSensors NIST pre-calibrated with certificate of calibration; field replaceable
Operating Environment-4 to 122 deg F (-20 to 50 deg C); 15-95% RH continuous, 0-95% intermittent; max. elevation 6,562 ft (2000 m)
MountingWall
Enclosure MaterialABS/polycarbonate
Dimensions4.0 x 4.4 x 2.1 in. (H x W x D)
Conduit OpeningTapped 1/2 in. NPT
Enclosure RatingIP43 or NEMA 3R
ComplianceUL61010-1 listed; UL, cUL, CE