TC320B-G

SKU: TC320BG
$354.15

This item is IN STOCK

Current Stock: 43

Details

Details

Controlco Product Information Tabs
Product DetailsSpecificationsDownloads

Product Information


Thermostat - FCU - 4 Pipe/2 Pipe, 2H/1C Heat Pump (air/water source), 1H/1C, 2H or 2C Conventional, BACnet MSTP, Modbus RTU, Sylk, Color Display.

The TC300 thermostat supports building automation connectivity via Wi-Fi or RS485 using BACnet or Modbus, suitable for most commercial applications. Highly configurable, it supports a wide range of equipment configurations including 2/4-pipe FCU, 1H/1C, 2H, 2C conventional, and 2H/1C heat pump plus water source heat pump. Standard onboard sensors include temperature and humidity, with options for occupancy + ambient light or CO2.


Features and Highlights


Convenient for Users

• Color capacitive‑touch screen display for intuitive commissioning and user experience.
• Embedded system monitoring screen for equipment and I/O status.
• Customizable inactive display modes: auto dim, always on, or dark mode.
• LED ring indicator shows operational status.
• Flexible schedule configurations: commercial, residential, fixed setpoint, or hospitality.
• Supports multiple languages: English, French, German, Italian, Spanish.

Fast and Flexible Commissioning

• Fast commissioning via Honeywell Connect Mobile app (Wi-Fi models only).
• Supports 2/4 pipe fan coil, 1H/1C, 2H, 2C conventional, 2H/1C air/water source heat pump.
• 1–3 or variable speed fan.
• Dehumidification with/without reheat.
• Service mode for manual output enabling and diagnostics.
• Auxiliary heating options for supplemental types.
• Auto mode for heating/cooling switching based on space temperature.
• Staging control, PID tuning, DAT lockout, modulating control, compressor time delay.
• Integration with external sensors (Discharge air, occupancy, CO₂, etc.).
• Complies with ASHRAE guideline 36‑2021 Section 5.22 for high‑performance operation.

Connected for Facility Managers

• Configurable user types with customizable privileges.
• Customizable daily schedules with up to 10 recurring holidays and 10 special events.
• Up to 4 schedule events per day.
• Flexible fan speed settings for residential scheduling.
• Non-programmable scheduling and Wi‑Fi configuration.

Specifications


Electrical Characteristics

Part NumberPower SupplyStandby Power ConsumptionMax. LoadRated Impulse VoltageDO+DIO Max. Current Limit
TC300B-G, TC320B-G, TC303B-G, TC321B-G, TC322B-G24 VAC 50/60 Hz (20-30 VAC)1.5 VA @ 24 VAC96 VA (all DOs ON)500 VTotal =4 A
TC300C-G1, TC320C-G1, TC303C-G, TC321C-G, TC322C-G100-240 VAC 50/60 Hz3.3 VA @ rated voltage1200 VA @ 120 VAC; 2400 VA @ 240 VAC; 2770 VA @ 277 VAC4 kV (Overvoltage Cat III)Total =10 A
TC300C-G, TC320C-G100-277 VAC 50/60 Hz3.3 VA @ rated voltage1200 VA @ 120 VAC; 1500 VA @ 240/277 VAC2.5 kV (Overvoltage Cat II)Total =10 A

User Interface

Display TypeCapacitive touch TFT, 320-240 px, 2.4" diag.
BacklightLCD (dimmable)
LED Color RingBlue (cooling), Orange (heating)

Operating Environment

Ambient Operating Temperature32-122°F (0-50°C)
Ambient Operating Humidity10-90% RH, non-condensing
Storage Temperature-40-150°F (-40-65.5°C)
Protection ClassIP20
Pollution Degree2
Operation MethodType 1.B Action

Technical Specifications - Onboard Sensors

ParameterSpecifications
Temperature Accuracy+/-1.5°F (0.8°C) from 32-122°F (0-50°C); +/-0.9°F (0.45°C) with 95% confidence from 60-85°F (15-30°C)
Temperature Control Accuracy+/-1.5°F (0.8°C) from 60-85°F (15-30°C), all models
Temperature Display Precision1°F (0.5°C), all models
Humidity Accuracy+/-3% RH from 20-80% RH @ 25°C (most models); +/-3.5% RH for TC320B-G
Humidity Display Precision1% RH, all models
CO2 Accuracy+/-30 ppm +/-3% of reading between 400-5000 ppm (specific models)
CO2 Output Resolution1 ppm
Occupancy Sensor61 GHz Doppler Radar, 120° horizontal field, max 8 m center, 6 m edge

Technical Specifications — Compliances

SKUCertificatesStandards
TC300B-G, TC303B-G, TC300C-G1, TC303C-GCE, FCC, ICES, UL/CUL, RoHS, REACH, Prop65EN 60730-1, EN 60730-2-9, UL60730-1, UL60730-2-9, 47 CFR Part 15 Subpart B, ICES-003
TC320B-G, TC321B-G, TC322B-G, TC320C-G1, TC321C-G, TC322C-GEN 60730-1, EN 60730-2-9, UL60730-1, UL60730-2-9, 47 CFR Part 15 Subpart B & C, ICES-003, RSS247, EN 300 328, EN 301 489-1, EN 301 489-17, EN 62479, EN 62311
TC303B-G, TC322B-G, TC303C-G, TC322C-GRadarEN305 550 Part 15C 15.255 RSS210
TC300C-GEN 60730-1, EN 60730-2-9, 47 CFR Part 15 Subpart B, ICES-003
TC320C-GCE, FCC, ICES, RoHS, REACH, Prop65EN 60730-1, EN 60730-2-9, 47 CFR Part 15 Subpart B & C, ICES-003, RSS247, EN 300 328, EN 301 489-1, EN 301 489-17, EN 62479, EN 62311

Technical Specifications — Wired and Wireless Technologies

FeatureSpecifications
Sylk™Honeywell Sylk™, 2-wire bus
BACnet MS/TPRS485 (9.6, 19.2, 38.4, 76.8, 115.2 kbps)
Modbus RTURS485 (1.2–115.2 kbps)
BACnet IP (TC32XB/TC32XC)Over Wi-Fi
Wi-Fi 2.4 GHz (TC32XB/TC32XC)IEEE802.11 b/g/n; security: NONE, WPA_PSK, WPA_WPA2_PSK, WPA2_PSK, WPA2_WAP3_PSK, WPA3_PSK
Bluetooth (TC32XB/TC32XC)BLE 5.3 Class 2; IEEE802.15.4 Open Thread

TC300 Models

SKUInput PowerWirelessSensorsWired CommunicationsEquipment CompatibilityInputs/Outputs
TC300B-G24 VACNoTemperature, HumidityRS485 (BACnet MS/TP, Modbus RTU)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional3 × DO (24 VDC), 2 × DIO, 3 × UIO
TC303B-G24 VACNoTemperature, Humidity, CO₂, Occupancy & LightRS485 (BACnet MS/TP, Modbus RTU)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional3 × DO (24 VDC), 2 × DIO, 3 × UIO
TC320B-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, HumidityRS485 (BACnet MS/TP, Modbus RTU)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional3 × DO (24 VDC), 2 × DIO, 3 × UIO
TC321B-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, Humidity, CO₂RS485 (BACnet MS/TP, Modbus RTU)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional3 × DO (24 VDC), 2 × DIO, 3 × UIO
TC322B-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, Humidity, Occupancy & LightRS485 (BACnet MS/TP, Modbus RTU)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional3 × DO (24 VDC), 2 × DIO, 3 × UIO
TC300C-G1120–277 VACNoTemperature, HumidityFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC303C-G120–277 VACNoTemperature, Humidity, CO₂, Occupancy & LightFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC300C-G120–277 VACNoTemperature, HumidityFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC320C-G1Wi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, HumidityFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC320C-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, HumidityFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC321C-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, Humidity, CO₂FCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO
TC322C-GWi-Fi (BACnet IP, Connect Me App, Connect Mobile App)NoTemperature, Humidity, Occupancy & LightFCU (2/4 pipe)FCU (2/4 pipe), 2H/1C heat pump (air/water source), 1H/1C, 2H or 2C conventional5 × DO (110–277 VAC), 3 × UIO