SXWHHREL10001

SKU: SXWHHREL10001
$275.93

Call for Availability - (510) 636-7900

Details

Details

10-Channel Relay Expansion Module for Lights and Blinds, 12 Digital Inputs, RP-C Room Bus

Adds 10 relay outputs and 12 dry-contact inputs to an RP-C room controller over the room bus. Takes power and communications from the RP-C, sold separately. Shares its room bus (236 ft max) with up to 5 other expansion modules. Drives 120/240 VAC blind motors directly and other blind motors through external relays.

Key Features

  • Relay ratings: 24-277 VAC, 10A resistive, 5A LED driver
  • Digital inputs: 12 dry contact, SELV
  • Mounting: DIN rail or flat surface
  • Plenum: UL 2043

Product Specifications

ManufacturerSchneider Electric
ModelSXWHHREL10001 (CRS-HH-REL-10)
Product rangeSpaceLogic Connected Room Solution, RP Series expansion relay module
Host controllerRP-C room controller; power and communications over the room bus
Relay outputs10 (DO1-DO10), 24 to 277 VAC 50/60 Hz or 30 VDC
Relay ratingsResistive and incandescent 10 A; standard magnetic ballast 5 A; LED driver 5 A; 1/2 HP at 240 VAC; 1/4 HP at 120 VAC
Maximum load current50 A total for the 10 outputs
Maximum inrush current165 A (<20 ms) per output; 800 A (<200 us) per output
Blind motors120/240 VAC motors directly; other types through external relays
Digital inputs12 (DI1-DI12), dry contact, 0 to 5.0 VDC, 2.2 mA, SELV
Power24 VDC from the RP-C over the room bus (RJ45)
Power consumption0.3 W max
Room busRS-485; dual RJ45 ports for daisy chain; Cat 5 or higher cable; 236 ft (72 m) max total length; up to 6 expansion modules per RP-C
Room bus protectionTransient voltage suppressors on communication and power signals
AddressingRotary switch 0 to 9; set push-button
Status indicatorGreen and red LED
Terminal blocksPluggable screw terminals included: relay outputs 10 x 2-pin, digital inputs 2 x 9-pin
Terminal torque2-pole connector 4.4 lb-in (0.5 Nm); 9-pole connector 1.7 lb-in (0.2 Nm)
ProcessorARM Cortex-M4 single-core, 80 MHz; 320 KB SRAM, 512 KB flash, 16 MB NOR flash
Software compatibilityEcoStruxure Building Operation 3.3 and later
MountingDIN rail or flat surface
Dimensions7.8 x 4.3 x 2.5 in. (198 x 110 x 64 mm), W x H x D
Weight1.050 lb (0.476 kg)
Operating conditions32 to 122 deg F (0 to 50 deg C), 20-90% RH non-condensing
Storage conditions-4 to 158 deg F (-20 to 70 deg C)
EnclosureIP20, UL94 V-0 plastic
PlenumApproved for plenum applications (UL 2043)
ListingsUL 916 C-UL US Listed (UL file E80146); FCC Part 15 Subpart B, Class B; ICES-003; CE; RCM; EN 60730-1, EN 60730-2-11, EN 50491-3