SM24A-MOD

SKU: SM24AMOD
$475.20

Call for Availability - (510) 636-7900

Details

Details

SM24A-MOD 180 lb-in Non-Spring Return Damper Actuator, 24 VAC/DC, BACnet/Modbus

Controlled over BACnet MS/TP, Modbus RTU, or MP-Bus, or by 2-10 VDC. Holds position on power loss.

Key Features

  • Running time: 86 to 346 s (selectable)
  • Shaft clamp: reversible 10 to 20 mm

Product Specifications

ManufacturerBelimo
ModelSM24AMOD (SM24A-MOD)
Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 to 28.8 V / DC 21.6 to 28.8 V
Power consumption in operation3.5 W
Power consumption in rest position1.4 W
Transformer sizing6 VA
Connection supply/controlcable 3 ft. (1 m), 6x 0.75 mm2
Communicative controlBACnet MS/TP Modbus RTU (factory setting) MP-Bus
Number of nodesBACnet / Modbus see interface description MP-Bus max. 8
Torque180 lb-in (20 Nm)
Torque variable25%, 50%, 75% reduced
Operating range Y2 to 10 V
Operating range Y variable0.5 to 10 V
Position feedback U2 to 10 V
Position feedback U noteMax. 1 mA
Position feedback U variableStart point 0.5 to 8 V End point 2 to 10 V
Position accuracy+/-5%
Direction of motion motorselectable with switch 0/1
Direction of motion variableelectronically reversible
Direction of motion noteY = 0%: At switch position 0 (ccw rotation) / 1 (cw rotation)
Manual overridewith push-button, can be locked
Angle of rotationMax. 95 deg
Angle of rotation notecan be limited on both sides with adjustable mechanical end stops
Running time (motor)150 s / 90 deg
Running time motor variable86 to 346 s
Noise level, motor45 dB(A)
Adaptation Setting Rangemanual
Override control, controllable via busMAX (maximum position) = 100%
CommunicationMIN (minimum position) = 0% ZS (intermediate position) = 50%
Override control variableMAX = (MIN + 32%)...100% MIN = 0%...(MAX – 32%) ZS = MIN...MAX
Mechanical interfaceUniversal shaft clamp reversible 10 to 20 mm
Position indicationMechanical, pluggable
Protection class IEC/ENIII, Safety Extra-Low Voltage (SELV)
Power source ULClass 2 Supply
Degree of protection IEC/ENIP54
Degree of protection NEMA/ULNEMA 2
HousingUL Enclosure Type 2
EMCCE according to 2014/30/EU
Certification IEC/ENIEC/EN 60730-1 and IEC/EN 60730-2-14
UL ApprovalcULus according to UL60730-1A, UL60730-2-14 and CAN/CSA E60730-1 The UL marking on the actuator depends on the production site, the device is UL-compliant in any case
Hygiene testAccording to VDI 6022 Part 1 / SWKI VA 104-01, cleanable and disinfectable, low emission
Type of actionType 1
Rated impulse voltage supply / control0.8 kV
Pollution degree3
Ambient humidityMax. 95% RH, non-condensing
Ambient temperature-22 to 122 deg F (-30 to 50 deg C)
Storage temperature-40 to 176 deg F (-40 to 80 deg C)
Servicingmaintenance-free
Weight2.2 lb (1.0 kg)