SE7200C5045
Details
Details
Zone Room Controller, 1 Heat/1 Cool, On/Off or Floating Outputs, Stand-Alone (Network Ready)
Controls heating or cooling hydronic valves. Switches 30 VAC max, 1A on its outputs. Needs 10-30 VAC power. Runs stand-alone; BACnet MS/TP needs the VCM7300V5000B communication card, sold separately.
Key Features
- Outputs: 2 universal, 1 digital
- Inputs: 2 dry contact
- PIR cover option: COV-PIR-ZN-5031, sold separately
Product Specifications
| Manufacturer | Schneider Electric |
|---|---|
| Model | SE7200C5045 |
| Series | SE7000 Series (SE7200) |
| Application | Zone thermostat |
| Equipment controlled | Low voltage zoning: heating or cooling hydronic valve and temperature control; reheat control, induction units, chilled beam, under floor heating, perimeter radiant heat |
| Heat/cool stages | 1 heat/1 cool |
| Output type | Floating or on/off |
| Network | Stand-alone (network ready) |
| Communication card | BACnet MS/TP: VCM7300V5000B communication card, sold separately (field upgrade) |
| Power | 10 to 30 VAC, 50/60 Hz; 2 VA |
| Sensors | Temp: 10k Type 2 NTC thermistor |
| Accuracy | Temp +/-0.9 deg F at 70 deg F, typical, calibrated |
| Setpoint range | 40 to 90 deg F (4 to 32 deg C) heating; 0.9 deg F per step; 54 to 100 deg F (12 to 38 deg C) cooling |
| Display range | -40 to 122 deg F |
| Inputs | 2 dry contact |
| Outputs | 2 x universal; 1 x digital |
| Output voltage | 30 VAC |
| Output current | 1 A max.; 3 A inrush |
| Proportional band | Adjustable P regulator, heating and cooling, 3.2 deg F factory setting |
| Economizer | No |
| Humidity control | No |
| PIR cover | No |
| Scheduling | No |
| Terminals | Screw terminal |
| PIR cover accessory | COV-PIR-ZN-5031 (SE7200 models), sold separately |
| Dimensions | 4.92 x 3.42 x 1.18 in. (124.97 x 86.87 x 29.97 mm), H x W x D |
| Weight | 0.75 lb (0.34 kg) |
| Wire gauge | 22 to 18 AWG |
| Operating temperature | 32 to 122 deg F (0 to 50 deg C) |
| Storage temperature | -22 to 122 deg F (-30 to 50 deg C) |
| Operating humidity | 0 to 95% RH, non-condensing |
| Insulation class | Class II |
| Certifications | FCC CFR 47 part 15 class A; CE; C-tick AS/NZS CISPR 22; UL listed file E27734 CCN XPAX; UL listed file E27734 CCN XPAX7; FCC part 15 Subpart B; UL 873; ICES-003; CSA C22.2 No 24 |
| Directives | 89/336/EEC - electromagnetic compatibility |
| Warranty | 18 months |