RIBL12BM
Details
Details
RIBL12BM Mechanically Latching Relay, 20A SPST, 12 VAC/DC Latch/Unlatch Coils, Auxiliary Contact
Latch and unlatch coils set the contact, which holds with no coil power. An auxiliary contact turns on when 120-277 VAC is present on the load wire. Larger NEMA 1 housing accepted for use in plenum, on a 0.50 in. NPT hub.
Key Features
- Auxiliary output: Auxiliary contact, 3A @ 30 VAC/DC max.
- Contact ratings: 20A resistive @ 120-277 VAC; 16A electronic ballast @ 120-277 VAC; 720 VA pilot duty @ 120-277 VAC
- Coil voltage: 12 VAC/DC, dual coil (latch and unlatch)
Product Specifications
| Manufacturer | Functional Devices |
|---|---|
| Model | RIBL12BM |
| Type | Mechanically latching relay, enclosed |
| Contacts | One SPST latching relay, dual coil |
| Contact ratings | 20A resistive @ 120-277 VAC; 16A electronic ballast @ 120-277 VAC; 720 VA pilot duty @ 120-277 VAC; 2 HP @ 277 VAC |
| Coil voltage | 12 VAC/DC, dual coil (latch and unlatch); min. 10 VDC / 11 VAC; 30 seconds max. pulse |
| Auxiliary output | Auxiliary contact, 3A @ 30 VAC/DC max.; contact and status LED activate when 120-277 VAC is present between Load and Load Neutral wires |
| Housing | NEMA 1, accepted for use in plenum |
| Dimensions | 2.39 in. H x 3.31 in. W x 1.81 in. D, with 0.50 in. NPT hub |
| Mounting | 0.50 in. NPT hub |
| Wires | 16 in. leads, 600 V rated |
| Operating temperature | -30 to 140 deg F |
| Approvals | UL Listed, UL60947, C-UL, CE, RoHS |
| Siblings | RIBL12B: no auxiliary contact; RIBL12SBM: adds true manual override; RIBL24BM: 24 VAC/DC coil |