RIBHX24BF
Details
Details
RIBHX24BF Enclosed Relay and AC Current Switch, 20A SPST, 24 VAC Coil, Fixed Trip Point
Relay and built-in current sensor in one gray NEMA 1 housing, accepted for use in plenum. The sensor status contact closes when load current is over 0.25A; there is no adjustment. Certified for use with ECMs; mounts on a 0.50 in. NPT hub.
Key Features
- Trip point: Fixed, 0.25A
- Contact ratings: 20A resistive @ 277 VAC; 20A ballast @ 277 VAC; 1,110 VA pilot duty @ 277 VAC
- Sensor output: Solid-state contact, 30 VAC/DC, 100 mA
Product Specifications
| Manufacturer | Functional Devices |
|---|---|
| Model | RIBHX24BF |
| Type | Enclosed relay and AC current switch combination |
| Contacts | One SPST (N/O), continuous duty coil |
| Contact ratings | 20A resistive @ 277 VAC; 20A ballast @ 277 VAC; 1,110 VA pilot duty @ 277 VAC; 2 HP @ 277 VAC |
| Coil voltage | 24 VAC; 50-60 Hz |
| Sensing range | 0.25-20A, internal AC current sensor with contact status |
| Trip point | Fixed, 0.25A |
| Sensor output | Solid-state contact, 30 VAC/DC, 100 mA |
| Application | Certified for use with ECMs |
| Housing | NEMA 1, gray, accepted for use in plenum |
| Dimensions | 1.70 x 2.80 x 1.50 in., with 0.50 in. NPT hub |
| Mounting | 0.50 in. NPT hub |
| Wires | 16 in. leads, 600 V rated |
| Operating temperature | -30 to 140 deg F |
| Approvals | UL Listed, UL916, C-UL, CE, RoHS |
| Siblings | RIBHX24BA: adjustable trip point; RIBHX24BF-RD: red housing; RIBHX24BF-N4: clear NEMA 4X housing |