PW31-X-010C-D
Details
Details
Senva PW31-X-010C-D 0-10 psid Wet Diff Pressure Transmitter, 4-20mA, LED Display
Measures wet differential pressure across one diaphragm, with no bypass valves. Rated for system line pressure up to 50 psig. Needs 15-35 VDC; the LED display adds up to 3.5 VDC of loop drop.
Key Features
- Pressure Connection: 1/4 in. NPT female
- Electrical Connection: DIN43650A
- Differential Overload Pressure: 150% FS
Product Specifications
| Manufacturer | Senva |
|---|---|
| Model | PW31-X-010C-D |
| Bypass | None (stand-alone transducer) |
| Differential Pressure Range | 0-10 psid |
| Max Line Pressure | 0-50 psig |
| Output | 4-20mA, 2-wire |
| Display | LED display (loop powered) |
| Power Supply | 15-35 VDC, 20mA max. |
| Operating Temperature (electronics) | -4 to 175 deg F (-20 to 80 deg C) |
| Compensated Range | 30 to 158 deg F |
| Media Compatibility | 316L SS compatible liquids and gases; fluororubber O-rings |
| Sensor Type | Micro-machined silicon strain gauge |
| Temp Coefficient (Zero and Span) | +/-1.7% FS/100 deg F (+/-1.5% FS/50 deg C) for units under 25 psi |
| Line Pressure Effect | Zero shift <= 0.0035% FS/psig line pressure |
| Differential Overload Pressure | 150% FS |
| Maximum Pressure | 500% FS (maximum gauge pressure to maintain 0.25% accuracy) |
| Accuracy | +/-0.25% FS |
| Sensor Enclosure | Laser welded housing, IP65 |
| Long Term Stability | +/-0.5% FS/year |
| Shock and Vibration | 30G; 5G @ 50 Hz; 10G peak |
| EMI/RFI Protection | Per CE requirements |
| Dimensions (transmitter only) | 4.52 in. H x 2.83 in. W |
| Pressure Connection | 1/4 in. NPT female |
| Electrical Connection | DIN43650A |
| Environmental | IP65 (installed with water-tight fittings); 1/2 in. conduit adapter included |
| Display Accuracy | 0.1% |
| Display Voltage Drop | <3.5 VDC |
| Display Sample Rate | 4/s |
| Display Rating | IP65 |
| Calibration | Calibration certificate included with every sensing element |
| Compliance | CE, RoHS |