PL-DT-CO2

SKU: PLDTCO2
$354.78

Call for Availability - (510) 636-7900

Details

Details

Prolon PL-DT-CO2 Duct CO2 Transmitter

Mounts outside the duct with a 6 in. sampling tube inserted.

Needs CO2 near normal (about 400 ppm) at least 1 hour a day for self-calibration; for 24-hour occupancy or spaces that stay high or low, turn self-calibration off and calibrate yearly.

Key Features

  • 0-2000 ppm, adjustable to 10000 ppm
  • 4-20mA (3-wire), 0-5V, or 0-10V
  • 24 VAC/DC
  • LCD display

Product Specifications

ManufacturerProlon
ModelPL-DT-CO2
MountingOutside the duct, sampling probe inserted
Probe0.88 x 6 in. (22.5 x 152 mm)
GasCarbon dioxide (CO2)
Sensor typeDual-channel NDIR
Measurement range0-2000 ppm, adjustable 1000-10000 ppm
Output4-20mA (3-wire), 0-5 or 0-10 VDC, field selectable
Power supply24 VDC +/-20% or 24 VAC +/-10% (non-isolated half-wave rectified)
Current consumptionCurrent output: 75 mA at 24 VDC, 150 mA at 24 VAC max; voltage output: 50 mA at 24 VDC, 100 mA at 24 VAC max
Output drive at 24 VDCCurrent: 550 ohm max; voltage: 10k ohm min
Sensor accuracy+/-(30 ppm + 3% of reading)
Transmitter accuracy+/-0.25% of span (including linearity, hysteresis and repeatability)
Temperature dependency+/-2.5 ppm/deg C
Response time20 s (T63)
Warm-up1 minute
Sensor lifeOver 15 years
Self-calibrationBuilt in; needs about 400 ppm for at least 1 hour a day. Turn off for 24-hour or constantly high/low spaces and calibrate yearly.
ProtectionReverse voltage and transient protected
Input voltage effectNegligible over specified operating range
WiringScrew terminal block, 14-22 AWG
Operating conditions32 to 122 deg F (0 to 50 deg C), 5-90% RH non-condensing
Storage-40 to 158 deg F (-40 to 70 deg C)
ApprovalsCE
DisplayLCD, 1.4 x 0.6 in. (35 x 15 mm), 2 line x 8 character, alphanumeric; ppm, 0 to 10000 ppm
EnclosureGray polycarbonate, UL94-V0, IP65 (NEMA 4X), gasketed hinged cover; 1/2 in. NPT
Enclosure dimensions4.6 x 3.9 x 2.1 in. (116 x 100 x 54 mm)
Country of originCanada