PL-C1050-RTU

SKU: PLC1050RTU
$357.86

This item is IN STOCK

Current Stock: 5

Details

Details

Prolon PL-C1050-RTU Rooftop Unit Zoning Controller, 4 In / 5 Out

Acts as master on a Prolon zoning network. Order the PL-C1050-RTUS for a single-zone unit, or the PL-M2000-RTU for 9 inputs and up to 3 heat stages.

Key Features

  • Up to 2 heat and 4 cool stages, or full modulation
  • Preheat, morning warm-up, and cooling priority
  • Dehumidification with a Prolon humidity controller
  • Modbus RTU

Product Specifications

ManufacturerProlon
ModelPL-C1050-RTU
ApplicationRooftop units; master controller for Prolon zoning
InputsOutdoor, return, supply: 10k thermistor; external clock or proof of fan: dry contact
Digital outputs4 triac, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog output1 x 0-10, 2-10 or 0-5 VDC, 40 mA max (resettable fuse)
StagingUp to 2 heat and 4 cool stages, or full modulation
SequencesPreheat, morning warm-up, cooling priority, unoccupied modes; dehumidification when networked with a Prolon humidity controller
ProtectionBuilt-in protection sequences with configurable temperature limits and minimum delays
Supply24 VAC +/-10%, 50/60 Hz, Class 2
Power2 VA consumption, 32 VA input
CommunicationModbus RTU (RS485), up to 127 nodes
Baud rates9600, 19200, 38400, 57600, 76800, 115200
IndicationLEDs for each output, communication, power and microprocessor state
MicroprocessorPIC18F6722, 8-bit, 40 MHz, 128 KB flash
ConnectionRemovable screw terminal blocks, 16 AWG max
CasingMolded ABS, UL94-HB
Dimensions6.2 x 5.2 x 2.5 in. (157 x 132 x 64 mm)
Weight0.85 lb (0.39 kg)
Environment-4 to 122 deg F (-20 to 50 deg C), non-condensing
CertificationUL916, CAN/CSA-C22.2, RoHS, FCC Part 15 Class B