PL-C1050-FCU

SKU: PLC1050FCU
$357.86

Call for Availability - (510) 636-7900

Details

Details

Prolon PL-C1050-FCU Fan Coil Controller, 4 In / 5 Out

Controls 2-pipe or 4-pipe hydronic fan coils from one space sensor. Changes over automatically on water temp on 2-pipe units.

Key Features

  • Multi-speed fan control
  • On/off or PWM aux heat output
  • Coil purge cycle
  • Modbus RTU

Product Specifications

ManufacturerProlon
ModelPL-C1050-FCU
Application2-pipe or 4-pipe hydronic fan coils, single space sensor
InputsOutdoor air temp, supply air temp, supply water temp; dry contact for proof of fan or leak alarm
Digital outputs4 triac, 10-30 VAC source or sink, 300 mA max (self-resetting fuse)
Analog output1 x 0-10, 2-10 or 0-5 VDC, 40 mA max (self-resetting fuse)
Sequences2-pipe automatic changeover on water temp, coil purge, modulating heating valve, on/off heating and/or cooling, multi-speed fan, on/off or PWM aux heat, unoccupied modes
LimitsSeveral configurable safety and efficiency limits
Supply24 VAC +/-10%, 50/60 Hz, Class 2
Power2 VA consumption, 32 VA input
CommunicationModbus RTU (RS485), up to 127 nodes
Baud rates9600, 19200, 38400, 57600, 76800, 115200
IndicationLEDs for each output, communication, power and microprocessor state
MicroprocessorPIC18F6722, 8-bit, 40 MHz, 128 KB flash
ConnectionRemovable screw terminal blocks, 16 AWG max
CasingMolded ABS, UL94-HB
Dimensions6.2 x 5.2 x 2.5 in. (157 x 132 x 64 mm)
Weight0.85 lb (0.39 kg)
Environment-4 to 122 deg F (-20 to 50 deg C), non-condensing
CertificationUL916, CAN/CSA-C22.2, RoHS, FCC Part 15 Class B