PL-C1050-FCU
Details
Details
Prolon PL-C1050-FCU Fan Coil Controller, 4 In / 5 Out
Controls 2-pipe or 4-pipe hydronic fan coils from one space sensor. Changes over automatically on water temp on 2-pipe units.
Key Features
- Multi-speed fan control
- On/off or PWM aux heat output
- Coil purge cycle
- Modbus RTU
Product Specifications
| Manufacturer | Prolon |
|---|---|
| Model | PL-C1050-FCU |
| Application | 2-pipe or 4-pipe hydronic fan coils, single space sensor |
| Inputs | Outdoor air temp, supply air temp, supply water temp; dry contact for proof of fan or leak alarm |
| Digital outputs | 4 triac, 10-30 VAC source or sink, 300 mA max (self-resetting fuse) |
| Analog output | 1 x 0-10, 2-10 or 0-5 VDC, 40 mA max (self-resetting fuse) |
| Sequences | 2-pipe automatic changeover on water temp, coil purge, modulating heating valve, on/off heating and/or cooling, multi-speed fan, on/off or PWM aux heat, unoccupied modes |
| Limits | Several configurable safety and efficiency limits |
| Supply | 24 VAC +/-10%, 50/60 Hz, Class 2 |
| Power | 2 VA consumption, 32 VA input |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Indication | LEDs for each output, communication, power and microprocessor state |
| Microprocessor | PIC18F6722, 8-bit, 40 MHz, 128 KB flash |
| Connection | Removable screw terminal blocks, 16 AWG max |
| Casing | Molded ABS, UL94-HB |
| Dimensions | 6.2 x 5.2 x 2.5 in. (157 x 132 x 64 mm) |
| Weight | 0.85 lb (0.39 kg) |
| Environment | -4 to 122 deg F (-20 to 50 deg C), non-condensing |
| Certification | UL916, CAN/CSA-C22.2, RoHS, FCC Part 15 Class B |