PL-C1050-BLR
Details
Details
Prolon PL-C1050-BLR Boiler Controller, 4 In / 5 Out
Controls up to 2 boiler stages, or 1 modulating boiler with a backup stage. Order the PL-M2000-BLR for up to 4 stages.
Key Features
- Outdoor reset of supply water setpoint
- Lead-lag for pumps and boilers
- Optional 3-way valve sequence
- Modbus RTU
Product Specifications
| Manufacturer | Prolon |
|---|---|
| Model | PL-C1050-BLR |
| Application | Boiler plant: up to 2 stages, or 1 modulating boiler with optional backup stage |
| Inputs | Outside air, return water and supply water: 10k thermistor; proof of pump: dry contact |
| Digital outputs | 4 triac, 10-30 VAC source or sink, 300 mA max (resettable fuse) |
| Analog output | 1 x 0-10, 2-10 or 0-5 VDC, 40 mA max (resettable fuse), for the valve |
| Sequences | Outdoor reset of supply water setpoint, lead-lag for pumps and boilers, pump activity on outside temp or call for heat (or both), pump exercise, optional 3-way valve, setpoint offset from network demand or occupancy |
| Protection | Built-in protection sequences with configurable temperature limits and minimum delays |
| Supply | 24 VAC +/-10%, 50/60 Hz, Class 2 |
| Power | 2 VA consumption, 32 VA input |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Indication | LEDs for each output, communication, power and microprocessor state |
| Microprocessor | PIC18F6722, 8-bit, 40 MHz, 128 KB flash |
| Connection | Removable screw terminal blocks, 16 AWG max |
| Casing | Molded ABS, UL94-HB |
| Dimensions | 6.2 x 5.2 x 2.5 in. (157 x 132 x 64 mm) |
| Weight | 0.85 lb (0.39 kg) |
| Environment | -4 to 122 deg F (-20 to 50 deg C), non-condensing |
| Certification | UL916, CAN/CSA-C22.2, RoHS, FCC Part 15 Class B |