Senva P5-0500-1XX 0.1/0.25/2.5/5 in. WC Dry Pressure Transmitter
Measures dry air pressure on a selectable range, unidirectional or bidirectional, with a selectable current or voltage output. Comes without a duct probe; the RP-6 probe is sold separately. Needs 12-30 VDC or 24 VAC; one side of the transformer secondary is tied to signal common, so a dedicated transformer is recommended.
Key Features
- Auto-Zero Input: Push-button and NO contact closure
- Display: None
- Overpressure: 41.5 in. WC
Product Specifications
| Manufacturer | Senva |
|---|---|
| Model | P5-0500-1XX |
| Pressure Ranges | 0.1, 0.25, 2.5, or 5.0 in. WC unidirectional; +/-0.1, +/-0.25, +/-2.5, or +/-5.0 in. WC bidirectional (selectable) |
| Output | Selectable: 4-20mA loop powered, 4-20mA 3-wire, 0-5 VDC, 0-10 VDC |
| Accuracy | +/-1.0% of selected range (combined linearity and hysteresis) |
| Display | None |
| Duct Probe | None |
| Power Supply | 12-30 VDC or 24 VAC, 30mA max. |
| Auto-Zero Input | Push-button and NO contact closure |
| Operating Temperature | -4 to 140 deg F (-20 to 60 deg C) |
| Compensated Range | -4 to 140 deg F (-20 to 60 deg C) |
| Media Compatibility | Dry, oil-free air, N2 |
| Sensor Type | MEMS silicon piezoresistive; precision calibrated |
| Zero Tolerance | Included in accuracy specification |
| Span Tolerance | +/-1.00% |
| Zero Drift (1 year) | 0.004 in. WC/year max.; 0.4% for units over 0.5 in. WC |
| Thermal Shift (Zero and Span) | 0.01% FSO/deg F (0.02% FSO/deg C) measured from 72 deg F (22 deg C) |
| Overpressure | 41.5 in. WC |
| Max Static Line Pressure | 41.5 in. WC |
| Burst Pressure | 83 in. WC |
| Position Sensitivity | Non-position sensitive |
| Response Rate | 8 seconds (full scale) |
| Compliance | CE, RoHS |
| Enclosure Flammability | UL94 5VB |
| Enclosure Rating | NEMA 1 |
| LED Indication | Power heartbeat, auto-zero complete, 110% overpressure |
| Mounting | DIN mount, flat or side; conduit cover for 3/8 in. flex connectors |
| Dimensions (H x W x D) | 4.75 x 1.82 x 0.90 in. |
| Additional Probe | RP-6 remote/duct probe, 6 in. (sold separately); accepts 1/8 and 1/4 in. tubing |