M7410F3006
Details
Details
M7410F3006 Non-Spring Return Cartridge Globe Valve Actuator, 67.5 lbf, Modulating
Fits V5862A and V5863A 1, 1-1/4, and 1-1/2 in. cartridge globe valves only.
Holds its position on power loss.
Accepts a 0-10V or 2-10V control signal.
Needs 24 VAC power.
Key Features
- 1/4 in. stroke
- 4.9 ft (1.5 m) cable
- Direct/reverse acting switch
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | M7410F3006 |
| Product type | Cartridge globe valve actuator, non-spring return (Series 3000) |
| Stem force | 67.5 lb (300 N) |
| Stroke | 1/4 in. (6.5 mm) |
| Fail action | Non-spring return |
| Control signal | Modulating 0-10V or 2-10V (adjustable), 0.1 mA; direct/reverse acting switch |
| Input impedance | 100K ohms |
| Supply power | 24 VAC, +10/-30 percent, 50/60 Hz |
| Power consumption | 1.4 VA |
| Timing | 125 seconds at 60 Hz; 150 seconds at 50 Hz |
| Connections | 4.9 ft (1.5 m) cable |
| Mounting | Screws onto the valve body; no mounting tools |
| Medium | Water with maximum 50% glycol; controlled water temperature 36 to 230 deg F (2 to 110 deg C) |
| Operating temperature | 32 to 122 deg F (0 to 50 deg C) |
| Storage temperature | -40 to 158 deg F (-40 to 70 deg C) |
| Humidity | 5 to 95% RH (noncondensing) |
| Approvals | Underwriters Laboratories Inc. listed for plenum use (UL94-5V) |
| Weight | 5.6 oz (0.16 kg) |
| Fits | V5862A, V5863A Series 3000 cartridge globe valves, 1, 1-1/4, and 1-1/2 in. |
| Honeywell form | 63-2612-05 Rev. 02-13; 63-1293-03 Rev. 02-13 |