IO-R-34-TD

SKU: IOR34-TD

Call for Availability - (510) 636-7900

Details

Details

Controlco Product Information Tabs
Product DetailsSpecificationsDownloads

Product Information


JACE 8000 34 Point IO Module. Powered by 24VAC. Capable of powering 4 IO-R-16 modules. Connected to JACE 8000 or 9000 remotely over RS485


IO R is part of Tridium’s portfolio of hardware, software and tools designed for remote monitoring and control applications that enables end-to-end automation and device-to-enterprise integration. IO R allows a JACE® controller to interface directly with simple non-intelligent inputs and outputs remotely located up to 4,000 feet from the JACE. The connection is established via an industry-standard RS 485 multi-drop communications bus. Multiple IO R devices can be utilized on a single JACE, providing 250+ IO points on a single JACE.

Specifications


Niagra 4- Requires Niagra 4.3 or later
Niagra AX- Requires Niagra 3.8u3 or later

• 16 Universal inputs: Type 3 (10k) thermistors, 0-100k ohm, 0-10VDC, 0-20 mA with external resistor
• 10 Relay outputs (Form A contacts, 24 VAC @ 0.5 amp rated)
• 8 Analog outputs (0-10 VDC)
• Powered from a 24VAC/DC source
• Can power up to 4 IO-R-16 modules
• Connected to JACE remotely over a shielded RS485 bus

Power

One IO-R-34 can power four IO-R16 modules

Maximum Expansion

(8) IO-R-34s or (16) IO-R-16s

Mounting and Dimensions

The JACE IO modules support mounting on EN50022 standard 7.7mm · 35mm DIN rail or panel mounting
162mm (w) · 166mm (h) · 61mm (d)
6.8 in (w) · 4.5 in (h) · 2.4 in (d)

Agency Certifications

• UL 916
• C-UL
• CE EN 61326-1:2013
• RCM
• FCC part 15, class b
• RoHS2
• REACH
• WEEE
• China ROHS
• Open Energy Management Class 2