IO-R-16
Details
Details
16-Point Remote IO Module for JACE 8000/9000
Adds remote inputs and outputs to a JACE 8000 or JACE 9000 over a shielded RS-485 bus up to 4,000 ft away.
Draws 15 VDC power from an IO-R-34 or a separate 13.5-15.75 VDC supply.
Requires Niagara 4.3 or later on the JACE.
Key Features
- Universal inputs: 8; Type 3 (10k) thermistor, 0-100k ohm, 0-10 VDC, 0-20 mA (external resistor), dry contact, pulsing dry contact
- Relay outputs: 4, Form A, 24 VAC at 0.5A
- Analog outputs: 4, 0-10 VDC (2.5k ohm minimum load, 4 mA maximum)
Product Specifications
| Manufacturer | Tridium |
|---|---|
| Model | IO-R-16 |
| Product type | Remote IO module |
| IO points | 16 |
| Universal inputs | 8; Type 3 (10k) thermistor, 0-100k ohm, 0-10 VDC, 0-20 mA (external resistor), dry contact, pulsing dry contact |
| Relay outputs | 4, Form A, 24 VAC at 0.5A |
| Analog outputs | 4, 0-10 VDC (2.5k ohm minimum load, 4 mA maximum) |
| Power | 15 VDC from an IO-R-34, or a 13.5-15.75 VDC supply regulated within +/-4% |
| Power consumption | 0.133A / 2.0 W at 15 VDC (all relays on) |
| Max per JACE | 16 IO-R-16 (an IO-R-34 counts as two) |
| Communication | RS-485 multidrop to JACE COM1 or COM2, shielded bus |
| Bus distance | Up to 4,000 ft (1,200 m) from the JACE |
| Fits | JACE 8000, JACE 9000 |
| Niagara version | Niagara 4.3 or later; NiagaraAX 3.8u3 or later |
| Connectors | Two end-mounted 5-pin connectors for direct chaining |
| Mounting | EN50022 7.5 x 35 mm DIN rail or panel |
| Agency certifications | UL 916; C-UL; CE EN 61326-1:2013; RCM; FCC Part 15 Class B; RoHS2; REACH; WEEE; China RoHS; Open Energy Management Class 2 |
| Dimensions | 3.25 x 4.5 x 2.4 in. (82.5 x 116 x 61 mm) |
| Included | Grounding wire; eight 499-ohm resistors for 4-20 mA inputs |
| Tridium model | 14006 |