IO-R-16

SKU: IOR16

This item is IN STOCK

Current Stock: 2

Working with Niagara? Controlco is a Tridium-certified training partner. See Niagara 4 certification training.

Details

Details

16-Point Remote IO Module for JACE 8000/9000

Adds remote inputs and outputs to a JACE 8000 or JACE 9000 over a shielded RS-485 bus up to 4,000 ft away.

Draws 15 VDC power from an IO-R-34 or a separate 13.5-15.75 VDC supply.

Requires Niagara 4.3 or later on the JACE.

Key Features

  • Universal inputs: 8; Type 3 (10k) thermistor, 0-100k ohm, 0-10 VDC, 0-20 mA (external resistor), dry contact, pulsing dry contact
  • Relay outputs: 4, Form A, 24 VAC at 0.5A
  • Analog outputs: 4, 0-10 VDC (2.5k ohm minimum load, 4 mA maximum)

Product Specifications

ManufacturerTridium
ModelIO-R-16
Product typeRemote IO module
IO points16
Universal inputs8; Type 3 (10k) thermistor, 0-100k ohm, 0-10 VDC, 0-20 mA (external resistor), dry contact, pulsing dry contact
Relay outputs4, Form A, 24 VAC at 0.5A
Analog outputs4, 0-10 VDC (2.5k ohm minimum load, 4 mA maximum)
Power15 VDC from an IO-R-34, or a 13.5-15.75 VDC supply regulated within +/-4%
Power consumption0.133A / 2.0 W at 15 VDC (all relays on)
Max per JACE16 IO-R-16 (an IO-R-34 counts as two)
CommunicationRS-485 multidrop to JACE COM1 or COM2, shielded bus
Bus distanceUp to 4,000 ft (1,200 m) from the JACE
FitsJACE 8000, JACE 9000
Niagara versionNiagara 4.3 or later; NiagaraAX 3.8u3 or later
ConnectorsTwo end-mounted 5-pin connectors for direct chaining
MountingEN50022 7.5 x 35 mm DIN rail or panel
Agency certificationsUL 916; C-UL; CE EN 61326-1:2013; RCM; FCC Part 15 Class B; RoHS2; REACH; WEEE; China RoHS; Open Energy Management Class 2
Dimensions3.25 x 4.5 x 2.4 in. (82.5 x 116 x 61 mm)
IncludedGrounding wire; eight 499-ohm resistors for 4-20 mA inputs
Tridium model14006