HVFD3D3C0750G100C
Details
Details
HVFD3D3C0750G100C 3G SmartVFD, 75 HP, 460 VAC
Needs 3-phase 380 to 480 VAC power.
Runs 3-phase induction, permanent magnet, and synchronous reluctance motors.
Includes the graphic keypad.
Key Features
- 105A output current
- Frame C1
- BACnet, Modbus, FLN, N2
Product Specifications
| Manufacturer | Honeywell |
|---|---|
| Model | HVFD3D3C0750G100C |
| Product type | Variable frequency drive, 3G SmartVFD, drive only |
| Horsepower | 75 HP |
| Supply voltage | Nominal 460 VAC (380 to 480 VAC +/-10%) |
| Phase | 3-phase in, 3-phase out |
| Output current | 105A continuous at 440-480 VAC |
| Enclosure | IP21/NEMA 1 |
| Frame | C1 |
| Keypad | Graphic keypad |
| Options | Drive only |
| Supply frequency | 50/60 Hz +/-5% |
| True power factor | 0.9 or higher, nominal at rated load |
| Displacement power factor | Near unity (over 0.98) |
| Switching on input supply | Max 1 time per minute |
| Output voltage | 0-100% of supply voltage |
| Output frequency | 0-590 Hz |
| Switching on output | Unlimited |
| Ramp times | 1-3600 s |
| Efficiency | 0.98 at nominal current |
| Motor types | 3-phase induction, permanent magnet, and synchronous reluctance |
| Digital inputs | 6 total: 4 DI and 2 configurable DIO; PNP or NPN, 0-24 VDC, 28 VDC max |
| Pulse inputs | 2 (terminals 29 and 33), up to 110 kHz push-pull |
| Analog inputs | 2; -10 to +10V or 0/4-20mA, switch selectable; 10 bit plus sign |
| Analog outputs | 1; 0/4-20mA, 500 ohm max load, 8 bit |
| Digital outputs | 2 configurable DIO; 0-24V, 40 mA max; frequency output up to 32 kHz |
| Relay outputs | 2 programmable Form C. RO1: 240 VAC 2A resistive (NO and NC). RO2: NO 400 VAC 2A resistive, NC 240 VAC 2A resistive |
| Communication | RS-485 with BACnet, Modbus, FLN, and N2 built in; USB 1.1 type B |
| Auxiliary supplies | 24 VDC, 200 mA max; 10 VDC, 15 mA max |
| Control functions | Smart logic controller, four auto-tuning PID controllers, real-time clock, fire override mode |
| Protection | DC-link reactor; overvoltage and undervoltage trip; ground fault; mains and motor phase supervision; overcurrent and overtemperature; motor overload, stall, and underload; short-circuit protection of 24V and 10V supplies |
| Speed control range | 1:100 of synchronous speed (open loop) |
| Operating temperature | Max 122 deg F (50 deg C), 24-hour average max 113 deg F (45 deg C); min 32 deg F (0 deg C) at full rating, 14 deg F (-10 deg C) at reduced performance |
| Storage temperature | -13 to 149/158 deg F (-25 to 65/70 deg C) |
| Humidity | 5-93% RH, noncondensing (IEC 721-3-3 Class 3K3) |
| Altitude | 3,300 ft (1000 m) without derating |
| Vibration | 1.0 g |
| Installation environment | Overvoltage category III, pollution degree 2 (EN 60664-1); H2S class Kd (IEC 60068-2-43) |
| Approvals | CE; cULus Listed |
| Short-circuit current rating | 100,000 A rms symmetrical, with the recommended fuses |
| EMC standards | EN 61800-3 emission and immunity |
| Dimensions | 12.2 W x 27.3 H x 12.2 D in. |
| Weight | 99.2 lb |
| Included | Graphic keypad |
| Honeywell form | 31-00558-04 Rev. 07-26; 31-00559-01 |