HVFD3D3A0750G100C

SKU: HVFD3D3A0750G100C
$9,508.13
Request a Freight Quote

Ships by truck freight. Our sales team replies with delivered pricing, usually within one business day.

Details

Details

HVFD3D3A0750G100C 3G SmartVFD, 75 HP, 208/230 VAC

Needs 3-phase 200 to 240 VAC power.

Runs 3-phase induction, permanent magnet, and synchronous reluctance motors.

Includes the graphic keypad.

Key Features

  • 190A output current
  • Frame D1
  • BACnet, Modbus, FLN, N2

Product Specifications

ManufacturerHoneywell
ModelHVFD3D3A0750G100C
Product typeVariable frequency drive, 3G SmartVFD, drive only
Horsepower75 HP
Supply voltageNominal 208/230 VAC (200 to 240 VAC +/-10%)
Phase3-phase in, 3-phase out
Output current190A continuous at 230 VAC
EnclosureIP21/NEMA 1
FrameD1
KeypadGraphic keypad
OptionsDrive only
Supply frequency50/60 Hz +/-5%
True power factor0.9 or higher, nominal at rated load
Displacement power factorNear unity (over 0.98)
Switching on input supplyMax 1 time per 2 minutes
Output voltage0-100% of supply voltage
Output frequency0-590 Hz
Switching on outputUnlimited
Ramp times1-3600 s
Efficiency0.97 at nominal current
Motor types3-phase induction, permanent magnet, and synchronous reluctance
Digital inputs6 total: 4 DI and 2 configurable DIO; PNP or NPN, 0-24 VDC, 28 VDC max
Pulse inputs2 (terminals 29 and 33), up to 110 kHz push-pull
Analog inputs2; -10 to +10V or 0/4-20mA, switch selectable; 10 bit plus sign
Analog outputs1; 0/4-20mA, 500 ohm max load, 8 bit
Digital outputs2 configurable DIO; 0-24V, 40 mA max; frequency output up to 32 kHz
Relay outputs2 programmable Form C. RO1: NO 400 VAC 2A resistive, NC 240 VAC 2A resistive. RO2: NO 400 VAC 2A resistive, NC 240 VAC 2A resistive
CommunicationRS-485 with BACnet, Modbus, FLN, and N2 built in; USB 1.1 type B
Auxiliary supplies24 VDC, 200 mA max; 10 VDC, 15 mA max
Control functionsSmart logic controller, four auto-tuning PID controllers, real-time clock, fire override mode
ProtectionDC-link reactor; overvoltage and undervoltage trip; ground fault; mains and motor phase supervision; overcurrent and overtemperature; motor overload, stall, and underload; short-circuit protection of 24V and 10V supplies
Speed control range1:100 of synchronous speed (open loop)
Operating temperatureMax 122 deg F (50 deg C), 24-hour average max 113 deg F (45 deg C); min 32 deg F (0 deg C) at full rating, 14 deg F (-10 deg C) at reduced performance
Storage temperature-13 to 149/158 deg F (-25 to 65/70 deg C)
Humidity5-93% RH, noncondensing (IEC 721-3-3 Class 3K3)
Altitude3,300 ft (1000 m) without derating
Vibration1.0 g
Installation environmentOvervoltage category III, pollution degree 2 (EN 60664-1); H2S class Kd (IEC 60068-2-43)
ApprovalsCE; cULus Listed
Short-circuit current rating100,000 A rms symmetrical, with the recommended fuses
EMC standardsEN 61800-3 emission and immunity
Dimensions12.8 W x 35.2 H x 14.9 D in.
Weight216 lb
IncludedGraphic keypad
Honeywell form31-00558-04 Rev. 07-26; 31-00559-01