H934
Details
Details
Veris H934 3.5-135A VFD Current Switch + Command Relay
Learns normal current at each drive speed and alarms on a drop from belt loss or mechanical failure, not on a speed change. Detects belt loss from 34 to 75 Hz; gives on/off status only from 20 to 34 Hz. Runs its relay independently of the current switch.
Key Features
- Status output: NO 0.1A @ 30 VAC/DC
- Relay: SPST 5A @ 250 VAC resistive
- Coil: 24 VAC/DC
- Core: split-core, fits conductors up to 0.8 in.
Product Specifications
| Current Measurement Range | 3.5 to 135 A |
|---|---|
| Current Sensor type | Current Switch, AC |
| Electrical Wiring Size | 24 to 14 AWG (0.2 to 2.1 mm2) |
| Measurement Type | AC Current | VFD |
| Monitored Frequency Range | 20 to 75 Hz (on/off status 20-34 Hz; belt-loss indication 34-75 Hz) |
| Monitored Wire Size | 0.8" (21 mm) |
| Mounting | Split-Core |
| Operating Humidity | 10 to 90% RH, non-condensing |
| Operating Temperature | 5 to 140 deg F (-15 to 60 deg C) |
| Output Specifications | NO 0.1 A @ 30 VAC/DC |
| Outputs | Switch output | Relay |
| Product Certification | UL |
| Relay Coil Voltage | 24 VAC/DC |
| Relay Construction | Mechanical |
| Relay Contact Ratings | Resistive: 5 A @ 250 VAC | Resistive: 5 A @ 30 VDC |
| Relay Poles/Throw | SPST |
| Setpoint | Self-adjusting trip point |
| Warranty | 5 years |
| Trip Point | 3.5 A or less; self-adjusting |
| Sensor Power | Induced from monitored conductor |
| Insulation Class | 600 VAC RMS |
| Off Delay | 0 sec to 2 min. |
| Relay Isolation | Relay isolated from the current switch |
| Typical Coil Current | 10 mA (24 VAC or VDC) |
| Terminal Block Torque | 3.5 to 4.4 in-lb (0.4 to 0.5 N-m) |
| Agency Approvals | UL 508 open device listing, CAT III, Pollution Degree 2, basic insulation |