FS-IOT-BACW
Details
Details
BACnet IoT Gateway, Wi-Fi and Ethernet, 2 RS-485 Ports
Connects BACnet/IP and BACnet MS/TP networks to the MSA Grid cloud for remote monitoring, control, data collection, and alarms, with no point mapping.
Provides remote access to Ethernet BACnet devices through its embedded OpenVPN server.
Joins the network by Ethernet or Wi-Fi; the Wi-Fi antenna is included.
Key Features
- Up to 1,000 BACnet objects to the MSA Grid
Product Specifications
| Manufacturer | MSA Safety |
|---|---|
| Model | FS-IOT-BACW |
| Product family | FieldServer BACnet IoT Gateway |
| Ordering code | FS-IOT-BACW (Wi-Fi): two serial port model, includes Wi-Fi antenna |
| Function | Connects BACnet/IP and BACnet MS/TP devices to the MSA Grid cloud for remote monitoring, control, data collection, and alarming |
| Serial | RS-485, galvanically isolated |
| Baud rates | 9600, 19200, 38400, 57600, 76800 |
| Ethernet | 10/100BaseT, MDIX, DHCP |
| Wi-Fi | 802.11 b/g/n, 2.4 GHz, channels 1-11; SMA antenna; TKIP, WPA2, and AES encryption |
| Cloud capacity | Pushes up to 1,000 BACnet objects to the MSA Grid |
| Remote access | Embedded OpenVPN server for remote connection to Ethernet BACnet devices |
| Data outputs | MSA Grid dashboard; CSV, JSON, Webhooks, or RESTful API; MQTT to third-party clouds |
| Notifications | Cloud-based alarms by SMS and/or email |
| Tools | BACnet Explorer (local or remote browse and command); on-board diagnostics; web configuration; Toolbox diagnostic utility |
| Network | Configurable routing and firewall; HTTPS (TLS/SSL) on ports 80 and 443 to the cloud |
| Security | FieldSafe: web page authentication (self-signed certificates), user and password management |
| Power | 24 VAC, 0.125A or 12-24 VDC, 0.25A |
| Max power | 3 W at 12 VDC |
| Mounting | DIN rail mount included |
| Dimensions (H x W x D) | 4 x 1.1 x 2.7 in. (10.16 x 2.8 x 6.8 cm) |
| Weight | 0.4 lb (0.2 kg) |
| Operating temperature | -4 to 158 deg F (-20 to 70 deg C) |
| Humidity | 10-95% RH non-condensing |
| Approvals | CE and FCC Part 15; BTL Marked; UL 60950-1 and CAN/CSA C22.2; DNP 3.0 and Modbus conformance tested; RoHS3, UKCA, and WEEE compliant; PTCRB and CTIA |
| Warranty | 2 years from shipment |