FGVL-AVKX24-MFT
Details
Details
FGVL-AVKX24-MFT Flanged Globe Valve Retrofit Linkage and 450 lb Actuator, Electronic Fail-Safe, 24 VAC/DC, MFT
Fits existing flanged globe valves 2-1/2 to 6 in. with bonnets up to 2.3 in. diameter. Linkage and actuator ship assembled, with the valve mounting hardware.
Multi-function (MFT) control: 2-10 VDC with 2-10 VDC feedback, or set up for on/off, floating, or PWM. Stored energy drives it to its fail-safe position on power loss; fail direction is set with a switch.
Close-off depends on the valve; check it in Belimo RetroFIT+ documentation.
Key Features
- Actuating force motor: 2000 N (450 lb)
- Stroke: 1.25" (32 mm)
- Running Time (Motor): 90 s
- Running time fail-safe: <35 s
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | FGVLAVKX24MFT (FGVL-AVKX24-MFT) |
| Valve | FGVL |
| Fluid | chilled or hot water and steam |
| Fluid Temp Range (water) | Please Refer to Manufacturer's Valve Specifications |
| Mounting Position | 360 deg |
| Applicable valve size | 2.5 to 6" (65 to 150) |
| Hardware | SS and Nickel plated steel |
| Housing material | Die cast aluminium and plastic casing |
| Stem | 316 stainless steel |
| Stem adapter | steel/Aluminum |
| Frame, plate, base | aluminum, steel (fits competitor bonnets up to 2.3" dia.) |
| Collar | aluminum |
| Coupling | GF Nylon supplied |
| Suitable actuators, Non-Spring | EVB(X) RVB(X) |
| Suitable actuators, Electrical fail-safe | AVKB(X) |
| Linkage weight | 9.0 lb (4.1 kg) |
| Actuator | AVKX24-MFT |
| Nominal voltage | AC/DC 24 V |
| Nominal voltage frequency | 50/60 Hz |
| Power consumption in operation | 5 W |
| Power consumption in rest position | 2 W |
| Transformer sizing | 9.5 VA (class 2 power source) |
| Electrical Connection | 18 GA plenum cable, 3 ft (1 m), with 1/2" conduit connector, degree of protection NEMA 2 / IP54 |
| Overload Protection | electronic throughout full stroke |
| Electrical Protection | actuators are double insulated |
| Actuating force motor | 2000 N (450 lb) |
| Operating range Y | 2 to 10 V |
| Operating range Y note | 4 to 20 mA w/ ZG-R01 (500 ohm, 1/4 W resistor) |
| Input Impedance | 100k ohm for 2 to 10 V (0.1 mA), 500 ohm for 4 to 20 mA, 1500 ohm for PWM, On/Off and Floating point |
| Operating range Y variable | Start point 0.5 to 30 V End point 2.5 to 32 V |
| Options positioning signal | variable (VDC, PWM, on/off, floating point) |
| Position feedback U | 2 to 10 V |
| Position feedback U note | Max. 0.5 mA |
| Position feedback U variable | VDC variable |
| Bridging time (PF) | 2 s |
| Pre-charging time | 5 to 20 s |
| Direction of motion motor | selectable with switch |
| Direction of motion fail-safe | reversible with switch |
| Manual override | 5 mm hex crank (3/16" Allen), supplied |
| Stroke | 1.25" (32 mm) |
| Running Time (Motor) | 90 s |
| Running time motor variable | 90 to 150 s |
| Running time fail-safe | <35 s |
| Noise level, motor | 60 dB(A) |
| Noise level, fail-safe | 60 dB(A) |
| Position indication | Mechanically, with pointer |
| Degree of protection IEC/EN | IP54 |
| Degree of protection NEMA/UL | NEMA 2 |
| Enclosure | UL Enclosure Type 2 |
| Agency Listing | cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU |
| Quality Standard | ISO 9001 |
| Ambient temperature | -22 to 122 deg F (-30 to 50 deg C) |
| Storage temperature | -40 to 176 deg F (-40 to 80 deg C) |
| Ambient humidity | Max. 95% RH, non-condensing |
| Servicing | maintenance-free |