EP2120S
Details
Details
Veris EP2120S 3-15/0-20 psig EP Transducer, Manual-Mode Alarm
Outputs 3-15 or 0-20 psig branch pressure from a 4-20mA, 0-5V, or 0-10V input. Needs 15 ft min tubing or AA45.
Key Features
- Alarm: manual-mode, 100 mA @ 30 VAC/DC
- Manual override: set and hold
- Supply: 45 psig max, clean dry air
Product Specifications
| Measurement Type | EP transducer |
|---|---|
| Input Power | Class 2; 24 VAC/DC nominal, 30 VAC max; 150 mA max |
| Control Input | Class 2; 4-20mA/0-5V/0-10V, jumper-selectable |
| Input Impedance | 4-20mA: 250 ohm; 0-5V/0-10V: 10k ohm |
| Control Range | 0-20 psig or 3-15 psig, jumper-selectable |
| Calibration | 3-15 psi 5-point; 0-20 psi 6-point |
| Alarm Contact | Manual-mode alarm, 100 mA @ 30 VAC/DC |
| Fail Safe | None |
| Manual Override | Jumper-selectable mode, digital pushbutton adjust; set and hold |
| Pressure Indication | Electronic, 3-1/2 digit LCD |
| Accuracy | 1% FS; combined linearity, hysteresis, repeatability |
| Compensated Temp Range | 25 to 140 deg F (-4 to 65 deg C) |
| Temperature Coefficient | +/-0.05%/deg C |
| Operating Environment | 10 to 90% RH non-condensing |
| Air Capacity | 523 in3/min @ 45 psi (8570 cm3/min @ 310.3 kPa); 333 in3/min @ 20 psi (5456 cm3/min @ 137.9 kPa) |
| Supply Pressure | 45 psig max |
| Pressure Differential | 0.1 psig (supply to branch) |
| Minimum Tubing Length | 15 ft (use AA45 pneumatic capacitor for shorter runs) |
| Port Connection | 1/8 in. I.D. poly tubing |
| Media Connection | Clean, dry air, or inert gas. Do not use with oxygen service |
| Mounting | Standard SnapTrack |
| Cover Plate | Not included (AA43 sold separately) |
| Dimensions | 3.5 x 3.3 x 1.8 in. (89 x 84 x 46 mm) |
| EMC Conformance | CE option: Low voltage directive 2014/35/EU; EMC directive 2014/30/EU; CE mark applies to cover models only |
| Handling | Sold as an open device; static sensitive |
| Warranty | 5 years |