CVB4024NS-VAV1

SKU: CVB4024NSVAV1

Call for Availability - (510) 636-7900

Working with Niagara? Controlco is a Tridium-certified training partner. See Niagara 4 certification training.

Details

Details

Stryker BACnet Configurable VAV Controller, 4 UI, 2 AO, 4 DO, Airflow Sensor

Configured, not programmed, in Niagara with the Stryker tool for single-duct VAV.

Includes the microbridge airflow sensor but no actuator.

Takes TR71/TR75 Sylk wall modules on its Sylk bus.

Key Features

  • 4 universal inputs
  • 2 analog outputs
  • 4 triac outputs
  • 0-1.5 in. H2O airflow sensor
  • BACnet MS/TP, Sylk

Product Specifications

ManufacturerHoneywell
ModelCVB4024NS-VAV1
Product typeConfigurable VAV controller
Universal inputs4: 20k NTC, C7031G, C7041F, PT1000, TR23 setpoint, 100 ohm-100k ohm resistive, 0-10V, dry contact
Analog outputs2, 4-20mA (550 ohm max) or 0-10V (10 mA max), configurable as digital
Digital outputs4 triac, 20-30 VAC, 25-500 mA continuous, 800 mA for 60 ms
Airflow sensorMicrobridge, 0-1.5 in. H2O (0-374 Pa)
CommunicationBACnet MS/TP, 9.6-115.2 kbps, up to 30 controllers per segment; Sylk bus
Processor32-bit ATMEL ARM 7
Memory512 KB flash, 128 KB RAM
ClockReal-time clock, 24-hour backup at 32-100 deg F
External sensor power20 VDC +/-10% at 75 mA
Supply power20-30 VAC, 50/60 Hz
Power consumption5 VA controller only; 100 VA with all connected loads
Operating temperature32-122 deg F (0-50 deg C)
MountingPanel or DIN rail (EN50022), any orientation
Dimensions6-1/4 x 4-13/16 x 2-1/4 in. (159 x 122 x 57 mm)
ApprovalsUL/cUL (E87741) UL 916, plenum rated; CSA (LR95329-3); FCC Part 15 Subpart B Class B; Canadian C108.8; CE EMC 2014/30/EU; RoHS 2011/65/EU; RCM; BTL B-ASC
Honeywell form31-00100-03 Rev. 10-16