CO2-010-D
Details
Details
Duct CO2 Transmitter, 0-2000 ppm, 0-10V Output
Needs 18 to 30 VAC or 18 to 42 VDC power. Does not work in greenhouses, wineries, breweries, or other applications with industrial sources of CO2.
Key Features
- Response time: 3 minutes typical
Product Specifications
| Manufacturer | ACI |
|---|---|
| Model | CO2-010-D |
| ACI item number | 116282 |
| Gas detected | Carbon dioxide (CO2) |
| Sensing method | Single beam non-dispersive infrared (NDIR) absorption |
| Measurement range | 0 to 2000 ppm |
| Output signal | 0-10V (100 ohm output impedance) |
| Digital interface | RS-232 communication with UIP software |
| Supply voltage | 18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC |
| Power consumption | 1.65 W peak, 0.65 W average at 42 VDC (typical) |
| Accuracy | +/-40 ppm +3% of reading at 72 deg F (22 deg C) |
| Non-linearity | Under 1% of full scale at 72 deg F (22 deg C) |
| Stability | Under 2% of full scale over the life of the sensor (15 years typical) |
| Temp dependence | 0.2% of full scale per deg C |
| Pressure dependence | 0.13% of reading per mm Hg |
| Response time | 3 minutes typical for 90% step change |
| Calibration | ABC Logic self-calibration (automatic background calibration); no field calibration; does not work where the space is unoccupied less than 4 hours a day |
| Application limits | Not for greenhouses, wineries, breweries, or other applications with industrial sources of CO2 |
| Operating temp/RH range | 32 to 122 deg F (0 to 50 deg C), 0 to 95% RH non-condensing |
| Sensor coverage area | 7,500 sq ft maximum |
| Design life | 15 years |
| Agency approvals | CE and FCC part 15 class B; RoHS and WEEE compliant |
| Warranty | 2-year limited |