CO-R-RB-D

SKU: CORRBD
$562.02

Call for Availability - (510) 636-7900

Details

Details

Room CO Gas Detector, 0-125 ppm (0-250 ppm Adjustable), 4-20mA or 2-10V, 2 Relays, Buzzer, LCD

Needs 24 VAC or 24 VDC power. Takes 6300-0041 as its replacement sensor, rated about 5 years. Does not work with the Q4C II, M-Controller2, or Q-Controller, or on Modbus RTU.

Key Features

  • Relays: Two SPDT Form C dry contacts, 1A at 30 VDC / 0.5A at 125 VAC
  • Coverage area: 7500 sq ft; 49 ft radius
  • Mounting height: 4 to 6 ft above the floor
  • Response time: Under 60 seconds

Product Specifications

ManufacturerACI
ModelCO-R-RB-D
ACI item number107556
Gas detectedCarbon monoxide (CO), vehicle exhaust in non-hazardous areas
Sensor typeElectrochemical, wide spectrum, long life
Range0 to 125 ppm factory set; 0 to 250 ppm field adjustable
Accuracy+/-2.5% of reading
Repeatability+/-1% of reading
Response timeUnder 60 seconds for 90% of step change
Sensor lifeAbout 5 years under normal conditions
Replacement sensor6300-0041
Analog outputs4-20mA or 2-10V, jumper selectable
DisplayAlphanumeric LCD, 2 line x 8 digit; 2 red LEDs for relay status
RelaysTwo SPDT Form C dry contacts, 1A at 30 VDC / 0.5A at 125 VAC (resistive load)
Buzzer85 dB at one foot
Relay life expectancy200,000 cycles minimum at 1A, 30 VDC
Time delaysActuation / de-actuation 0 to 60 minutes in 5 minute increments
Coverage area7500 sq ft; 49 ft radius
Mounting height4 to 6 ft above the floor
CompatibilityNot compatible with the Q4C II, M-Controller2, or Q-Controller, or with Modbus RTU communication
Supply voltage24 VAC +/-10% floating or one side grounded; 24 VDC
Supply current100 mA nominal, 250 mA maximum
Power usage6.6 W maximum
Operating temp-4 to 104 deg F (-20 to 40 deg C)
Operating humidity15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing
Operating pressureAtmospheric +/-10%
Storage32 to 68 deg F (0 to 20 deg C)
Unit shelf life6 months from date of purchase
EnclosurePolycarbonate/ABS blend, UL94V-0, NEMA 1
Terminal blocks16 to 26 AWG shielded twisted pair; torque 0.37 ft-lb nominal
Calibration adapter83830-020-000 (sold separately)
Test intervalTest for accuracy and function every 6 months; verify and recalibrate when installed above 3000 ft
Dimensions (H x W x D)6.00 x 3.5 x 1.09 in. (152.4 x 88.9 x 27.87 mm)
Weight0.62 lb (281.2 g)
Warranty2-year limited; electrochemical sensor 6 months