C-2320
Details
Details
Senva C-2320 0.5-100A Split-Core Adjustable Current Switch
Sets its trip point by turning the dial to the motor nameplate full load amps, with no calibration in an energized enclosure. Opens its NO solid-state output (1A at 30 VAC/DC) on undercurrent such as belt loss or coupling shear. Gives on/off status only on VFD outputs from 12 to 115 Hz. Accepts a snap-on CR3 or CR4 command relay module, sold separately.
Key Features
- Turn-On Current: 0.5A
- Sensor Aperture: 0.75 x 0.75 in.
Product Specifications
| Manufacturer | Senva |
|---|---|
| Model | C-2320 |
| Current Range | 0.5-100A |
| Turn-On Current | 0.5A |
| Max Current | 100A |
| Core | Split-core |
| Trip Point | Adjustable; dial set to motor full load amps (FLA) from the nameplate |
| Output Type | NO, solid-state FET |
| Output Rating | 1A @ 30 VAC/DC |
| Sensor Power | Induced |
| Frequency Range | 50/60 Hz; on/off status for VFD outputs at 12 to 115 Hz |
| Sensor Aperture | 0.75 x 0.75 in. |
| Dimensions (L x W x H) | 2.5 x 2.23 x 0.57 in. |
| LED Indication | Trip LED and power LED |
| Environmental Rating | 5 to 140 deg F (-15 to 60 deg C); 10-90% RH non-condensing |
| Insulation Class | 600V RMS; for insulated conductors only; use minimum 75 deg C insulated conductor |
| Mounting | Clamps on conductor with iris, or detachable base for screw or DIN mount |
| Command Relay Option | Accepts CR3-24, CR4-24, CR3-12, or CR4-12 relay module (sold separately) |