B5-NO2-10P-O-X

SKU: B5NO210POX
$748.98

Call for Availability - (510) 636-7900

Details

Details

NO2 Gas Detector, 0-10 ppm, BACnet MS/TP, 3 Relays, LCD

Needs 24 VDC or 24 VAC power. Needs an accuracy and bump test every 6 months, or as code requires. Works indoors only, despite its NEMA 4X enclosure.

Key Features

  • Sensor life: 2 to 3 years typical (electrochemical)
  • Mounting height: Low: 0.5 to 1.5 ft (0.15 to 0.46 m) above floor

Product Specifications

ManufacturerACI
ModelB5-NO2-10P-O-X
ACI item number132864
Gas detectedNitrogen dioxide (NO2)
Sensor typeElectrochemical (toxic)
Measurement range0 to 10 ppm
Operating temp-4 to 122 deg F (-20 to 50 deg C)
Coverage area7500 sq ft (696.7 sq m) or 49 ft (14.9 m) radius
Mounting heightLow: 0.5 to 1.5 ft (0.15 to 0.46 m) above floor
Supply voltage24 VDC nominal (18 to 30 VDC) or 24 VAC nominal (15 to 24 VAC); AC power can be grounded or non-grounded
Communication protocolRS-485 serial BACnet MS/TP (master and slave; default master)
Baud rates9600, 19200, 38400, 76800 bits/second (default 38400)
Analog outputsNone (BACnet MS/TP only)
DisplayLCD graphic display with backlight (TWA, STEL, and concentration)
KeypadThree capacitive touch keys
RelaysThree SPDT (Form C) dry contacts, 1.0A max at 30 VDC or 0.3A max at 125 VAC (resistive)
Relay lifeMechanical 50,000,000 operations minimum at 36,000 operations/hour; electrical 200,000 operations minimum at rated load
Status LEDsTwo green (Tx/Rx communication); three relay LEDs (relays 1, 2, and 3)
Buzzer80 dB at 3.94 in. (10 cm), 2700 Hz, 3 programmable tones
Warm-up time24 hours (allow 24 hours before calibrating after installation)
Fuse protection0.750A polyswitch; resets after the fault is cleared and power is removed
Supply current / power0.3A maximum / 8.4 VA
EnclosurePolycarbonate (Lexan), UL94 V-0, NEMA 4, 4X, 12, and 13 (IP66)
Operating environmentIndoor use only
Enclosure knockouts3/4 in. knockouts (accept 1/2 in. conduit fittings)
Operating humidity5 to 95% RH, non-condensing
Operating atmospheric pressure14.696 psi (1.0132 bar) +/-10%; verify accuracy and recalibrate when installed above 3000 ft
Recommended storage32 to 68 deg F (0 to 20 deg C), 5 to 95% RH non-condensing
Wiring connectionsDe-pluggable screw terminal blocks, 16 to 24 AWG shielded twisted pair
Communications cableBelden 9841 or equivalent, 120 ohm
Terminal block torque0.37 ft-lb (0.502 Nm) nominal
Sensor life2 to 3 years typical (electrochemical)
Unit shelf life6 months from date of purchase
Recommended maintenanceAccuracy and bump test every 6 months or as required by code
ApprovalsRoHS; cETLus listed to CAN/CSA-22.2 No. 61010-1 and UL 61010-1 (Third Edition)
Dimensions (L x W x H)5.91 x 3.54 x 2.56 in. (150 x 90 x 65 mm)
Weight1.00 lb (0.454 kg)
Warranty2-year limited; electrochemical sensor module 6 months