B5-C3H8-100L-O-X
Details
Details
Propane Gas Detector, 0-100% LEL, BACnet MS/TP, 3 Relays, LCD
Needs 24 VDC or 24 VAC power. Needs an accuracy and bump test every 3 months, or as code requires. Works indoors only, despite its NEMA 4X enclosure.
Key Features
- Sensor life: 3 to 5 years typical (catalytic)
- Mounting height: Low: 0.5 to 1.5 ft (0.15 to 0.46 m) above floor
Product Specifications
| Manufacturer | ACI |
|---|---|
| Model | B5-C3H8-100L-O-X |
| ACI item number | 135364 |
| Gas detected | Propane (C3H8) |
| Sensor type | Catalytic (combustible) |
| Measurement range | 0 to 100% LEL (100% LEL = 2.1% by volume) |
| Operating temp | 14 to 122 deg F (-10 to 50 deg C) |
| Coverage area | 7500 sq ft (696.7 sq m) or 49 ft (14.9 m) radius |
| Mounting height | Low: 0.5 to 1.5 ft (0.15 to 0.46 m) above floor |
| Supply voltage | 24 VDC nominal (18 to 30 VDC) or 24 VAC nominal (15 to 24 VAC); AC power can be grounded or non-grounded |
| Communication protocol | RS-485 serial BACnet MS/TP (master and slave; default master) |
| Baud rates | 9600, 19200, 38400, 76800 bits/second (default 38400) |
| Analog outputs | None (BACnet MS/TP only) |
| Display | LCD graphic display with backlight (TWA, STEL, and concentration) |
| Keypad | Three capacitive touch keys |
| Relays | Three SPDT (Form C) dry contacts, 1.0A max at 30 VDC or 0.3A max at 125 VAC (resistive) |
| Relay life | Mechanical 50,000,000 operations minimum at 36,000 operations/hour; electrical 200,000 operations minimum at rated load |
| Status LEDs | Two green (Tx/Rx communication); three relay LEDs (relays 1, 2, and 3) |
| Buzzer | 80 dB at 3.94 in. (10 cm), 2700 Hz, 3 programmable tones |
| Warm-up time | 24 hours (allow 24 hours before calibrating after installation) |
| Fuse protection | 0.750A polyswitch; resets after the fault is cleared and power is removed |
| Supply current / power | 0.3A maximum / 8.4 VA |
| Enclosure | Polycarbonate (Lexan), UL94 V-0, NEMA 4, 4X, 12, and 13 (IP66) |
| Operating environment | Indoor use only |
| Enclosure knockouts | 3/4 in. knockouts (accept 1/2 in. conduit fittings) |
| Operating humidity | 5 to 95% RH, non-condensing |
| Operating atmospheric pressure | 14.696 psi (1.0132 bar) +/-10%; verify accuracy and recalibrate when installed above 3000 ft |
| Recommended storage | 32 to 68 deg F (0 to 20 deg C), 5 to 95% RH non-condensing |
| Wiring connections | De-pluggable screw terminal blocks, 16 to 24 AWG shielded twisted pair |
| Communications cable | Belden 9841 or equivalent, 120 ohm |
| Terminal block torque | 0.37 ft-lb (0.502 Nm) nominal |
| Sensor life | 3 to 5 years typical (catalytic) |
| Unit shelf life | 1 year from date of purchase |
| Recommended maintenance | Accuracy and bump test every 3 months or as required by code |
| Approvals | RoHS; cETLus listed to CAN/CSA-22.2 No. 61010-1 and UL 61010-1 (Third Edition) |
| Dimensions (L x W x H) | 5.91 x 3.54 x 2.56 in. (150 x 90 x 65 mm) |
| Weight | 1.00 lb (0.454 kg) |
| Warranty | 2-year limited; catalytic sensor module 1 year |