A/1K-2W-A-50'-4X
Details
Details
Copper Averaging Duct Temp Sensor, 1k Plat RTD, 2-Wire, 50 ft, NEMA 4X Box
Bends to follow the duct cross-section and enters through a 3/8 in. (9.53 mm) hole.
Mounts with the included nylon wire ties; copper capillary clips are sold separately.
Key Features
- Number of sensing points: Continuous (full length of the copper tube)
- Sensor operating range: -40 to 275 deg F (-40 to 135 deg C)
Product Specifications
| Manufacturer | ACI |
|---|---|
| Model | A/1K-2W-A-50'-4X |
| ACI item number | 136050 |
| Sensor type | Platinum RTD, PTC (positive temperature coefficient) |
| Sensor output | 1,000 ohm nominal @ 32 deg F (0 deg C) |
| Number of wires | Two (not polarity sensitive) |
| Accuracy | +/-0.1% @ 32 deg F (0 deg C); +/-0.25% @ 70 deg F (21 deg C); +/-1.0% @ 266 deg F (130 deg C) |
| Temperature coefficient | 3850 ppm/deg C |
| Response time | 15 seconds nominal (63% step change) |
| Self-heating | 4 mW/deg C (still air), 3 mA max |
| Number of sensing points | Continuous (full length of the copper tube) |
| Sensor operating range | -40 to 275 deg F (-40 to 135 deg C) |
| Averaging length | 50 ft (15.24 m) |
| Sensing element | Copper tube, 0.210 in. (5.34 mm) diameter nominal, bendable |
| Enclosure | Polystyrene plastic (4X), UL94-V2, NEMA 4X (IP66), -40 to 158 deg F (-40 to 70 deg C) |
| Storage range | -40 to 185 deg F (-40 to 85 deg C) |
| Operating humidity | 10 to 95% RH, non-condensing |
| Enclosure fitting | Polyamide 66 (nylon 66), UL94-HB |
| Foam pad | Neoprene/EPDM/SBR polymer, UL94-HBF, FMVSS-302, MIL-R-6130C |
| Lead wires | 12 in. (30.5 cm), 22 AWG, etched PTFE (Teflon) insulation, MIL-W-16878/4 Type E, silver-plated copper |
| Mounting | 3/8 in. (9.53 mm) hole in the duct; nylon wire ties and mounts included; copper capillary clips (A/CAPILLARY CLIP QTY:1) and plastic universal clips sold separately |
| Product weight | 3.36 lb (1.524 kg) |
| NIST certificate | Not included |
| Agency approvals | RoHS2, WEEE |