A/1K-2W-A-50'-4X

SKU: A1K2WA504X
$321.98

Call for Availability - (510) 636-7900

Details

Details

Copper Averaging Duct Temp Sensor, 1k Plat RTD, 2-Wire, 50 ft, NEMA 4X Box

Bends to follow the duct cross-section and enters through a 3/8 in. (9.53 mm) hole.

Mounts with the included nylon wire ties; copper capillary clips are sold separately.

Key Features

  • Number of sensing points: Continuous (full length of the copper tube)
  • Sensor operating range: -40 to 275 deg F (-40 to 135 deg C)

Product Specifications

ManufacturerACI
ModelA/1K-2W-A-50'-4X
ACI item number136050
Sensor typePlatinum RTD, PTC (positive temperature coefficient)
Sensor output1,000 ohm nominal @ 32 deg F (0 deg C)
Number of wiresTwo (not polarity sensitive)
Accuracy+/-0.1% @ 32 deg F (0 deg C); +/-0.25% @ 70 deg F (21 deg C); +/-1.0% @ 266 deg F (130 deg C)
Temperature coefficient3850 ppm/deg C
Response time15 seconds nominal (63% step change)
Self-heating4 mW/deg C (still air), 3 mA max
Number of sensing pointsContinuous (full length of the copper tube)
Sensor operating range-40 to 275 deg F (-40 to 135 deg C)
Averaging length50 ft (15.24 m)
Sensing elementCopper tube, 0.210 in. (5.34 mm) diameter nominal, bendable
EnclosurePolystyrene plastic (4X), UL94-V2, NEMA 4X (IP66), -40 to 158 deg F (-40 to 70 deg C)
Storage range-40 to 185 deg F (-40 to 85 deg C)
Operating humidity10 to 95% RH, non-condensing
Enclosure fittingPolyamide 66 (nylon 66), UL94-HB
Foam padNeoprene/EPDM/SBR polymer, UL94-HBF, FMVSS-302, MIL-R-6130C
Lead wires12 in. (30.5 cm), 22 AWG, etched PTFE (Teflon) insulation, MIL-W-16878/4 Type E, silver-plated copper
Mounting3/8 in. (9.53 mm) hole in the duct; nylon wire ties and mounts included; copper capillary clips (A/CAPILLARY CLIP QTY:1) and plastic universal clips sold separately
Product weight3.36 lb (1.524 kg)
NIST certificateNot included
Agency approvalsRoHS2, WEEE