7X-HS-K3W-X
Details
Details
75F HyperStat Thermostat with PM2.5 Sensor
Controls up to three stages of heat, cool, or fan, or modulating equipment. Measures room air quality with eight built-in sensors. Pairs with a 75F CCU, the wall-mounted head end of the system. Includes the PM2.5 particulate sensor.
Key Features
- 6 relays, 3 analog outputs
- 2 thermistor inputs, 2 0-10V inputs
- 24 VAC/DC power
Product Specifications
| Manufacturer | 75F |
|---|---|
| Model | 7X-HS-K3W-X |
| Equipment control | Up to 3 stages heat/cool/fan, or fully modulating; RTUs, heat pumps, 2-pipe fan coils, induction units, unit heaters, PTACs |
| Relays | (6) 24 VDC, 1A |
| Analog outputs | (3) 0-10V or 4-20mA, 20 mA max per channel |
| Thermistor inputs | (2) 10k Type 2 |
| Analog inputs | (2) 0-10V |
| Sensors | Temp, RH, CO2, light, sound, PIR occupancy; VOC and PM2.5/PM10 optional |
| Temperature | Temp range 32 to 122 deg F (0 to 50 deg C); +/-1 deg F typical |
| Humidity | Range 20 to 85% RH noncondensing; +/-2% RH typical |
| CO2 | Range 0-40,000 ppm; +/-30 ppm from 400-10,000 ppm |
| Occupancy | PIR, 4 m (13 ft) at 30 deg |
| Display | 2.8 in. TFT LCD, 240 x 320; touch slider and buttons |
| Wireless | 900 MHz IEEE 802.15.4 mesh; Bluetooth BLE 4.1 for commissioning |
| Wired | 4-wire RS485; 3-wire sensor bus connector |
| Power | 24 VAC/DC (+/-15%), 1.0 W nominal, 2.5 W max |
| Mounting | (2) screws in drywall |
| Dimensions | 6.5 x 4.5 x 1.15 in. (165 x 115 x 29 mm); wall plate 6.1 x 4.5 in. |
| Included | PM2.5 sensor |