22G15-5B5

SKU: 22G155B5
$982.80

Call for Availability - (510) 636-7900

Details

Details

22G15-5B5 CO2 Gas Monitor, 0-5000 ppm, 2 Relays, 0 Analog Outputs, BACnet MS/TP

Horn and strobe sound at alarm level 3; the LCD shows gas type, concentration, and alarm level.

Networks with other gas monitors over CAN bus.

Annual calibration required. Listed for 24 VAC power only under UL/CSA 61010-1. Not for hazardous locations or heavy industrial use.

Key Features

  • Mounting: 1 to 3 ft (0.3 to 0.9 m) below the ceiling
  • Coverage area: Radius: 50 ft (15 m)
  • Number of binary inputs: 1

Product Specifications

ManufacturerBelimo
Model22G155B5 (22G15-5B5)
Measured valuesCO2
Number of relays2
Number of analog outputs0
Number of binary inputs1
CommunicationCAN bus, BACnet MS/TP
Accuracy temperature+/-13 deg F @ 74 deg F (+/-7 deg C @ 23.5 deg C)
Nominal voltage24 VAC/DC
Nominal voltage frequency50/60 Hz
Nominal voltage range20 to 25 VAC / 22 to 34 VDC
Power consumption AC5 VA
Power consumption DC3.7 W
Cable entry2 top, 2 bottom, 1 rear - 1/2 in. EMT
Cable specificationCommunication cable: 22 to 24 AWG (0.34 to 0.25 mm2) twisted shielded pair, jacketed, 17 pF/ft or less, 100 to 120 ohm impedance, stranded cable
FuseThermal PTC, auto-reset
MediumAir
Relay outputSPDT, 5 A @ 240 VAC or 4 A @ 24 VAC, non-inductive, explosion proof, fail-safe
Mounting1 to 3 ft (0.3 to 0.9 m) below the ceiling
Max. altitude6562 ft (2000 m) above sea level
Max. altitude noteCalibration verification is recommended above 2000 ft (610 m)
Coverage areaRadius: 50 ft (15 m); Area: 7500 sq ft (700 sq m); There can be no obstructions such as walls, elevators, stairs, shelving with solid fill, tool chests, etc. Otherwise the time weighted average (TWA) for the gas to reach the monitor will increase.
DisplayLCD, with backlight with backlight showing gas type, gas concentration, alarm level status
AlarmAlarm level 1: Visual alarm (red LED) Alarm level 2: Visual alarm (red LED) Alarm level 3: Visual and audible alarm (flashing white strobe LED and horn); Horn: 80 dB @ 1 m (3.3ft)
Warm-up time10 minutes
Sensing element technology gasNon-dispersive infrared (NDIR) dual channel
Measuring range CO20 to 5000 ppm
CalibrationNon-interactive zero and span; Annual calibration required
Typical response time<105 s (T90)
Measuring range temperature-4 to 104 deg F (-20 to 40 deg C)
Agency ListingETL listed to UL 61010-1/-2-201, CSA C22.2#61010-1-12/-2-201; BTL listed to BTL-30001
Pollution degree2
Ambient humidity15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing
Ambient temperature-4 to 122 deg F (-20 to 50 deg C)
HousingUL94 5VA
Power rating under UL/CSA 61010-124 VAC only
Relay rating (UL/CSA tested)SPDT, 5 A @ 125 VAC, non-inductive
Weight0.95 lb (0.43 kg)