22G15-5A5 CO2 Gas Monitor, 0-5000 ppm, 1 Relay, 2 Analog Outputs, BACnet MS/TP
Horn and strobe sound at alarm level 3; the LCD shows gas type, concentration, and alarm level.
Networks with other gas monitors over CAN bus.
Annual calibration required. Listed for 24 VAC power only under UL/CSA 61010-1. Not for hazardous locations or heavy industrial use.
Key Features
- Mounting: 1 to 3 ft (0.3 to 0.9 m) below the ceiling
- Coverage area: Radius: 50 ft (15 m)
- Number of binary inputs: 1
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | 22G155A5 (22G15-5A5) |
| Measured values | CO2 |
| Number of relays | 1 |
| Number of analog outputs | 2 |
| Number of binary inputs | 1 |
| Communication | CAN bus, BACnet MS/TP |
| Accuracy temperature | +/-13 deg F @ 74 deg F (+/-7 deg C @ 23.5 deg C) |
| Nominal voltage | 24 VAC/DC |
| Nominal voltage frequency | 50/60 Hz |
| Nominal voltage range | 20 to 25 VAC / 22 to 34 VDC |
| Power consumption AC | 5 VA |
| Power consumption DC | 3.7 W |
| Cable entry | 2 top, 2 bottom, 1 rear - 1/2 in. EMT |
| Cable specification | Communication cable: 22 to 24 AWG (0.34 to 0.25 mm2) twisted shielded pair, jacketed, 17 pF/ft or less, 100 to 120 ohm impedance, stranded cable |
| Fuse | Thermal PTC, auto-reset |
| Medium | Air |
| Analog output | Analog outputs: 2 to 10 V or 4 to 20 mA default |
| Relay output | SPDT, 5 A @ 240 VAC or 4 A @ 24 VAC, non-inductive, explosion proof, fail-safe |
| Mounting | 1 to 3 ft (0.3 to 0.9 m) below the ceiling |
| Max. altitude | 6562 ft (2000 m) above sea level |
| Max. altitude note | Calibration verification is recommended above 2000 ft (610 m) |
| Coverage area | Radius: 50 ft (15 m); Area: 7500 sq ft (700 sq m); There can be no obstructions such as walls, elevators, stairs, shelving with solid fill, tool chests, etc. Otherwise the time weighted average (TWA) for the gas to reach the monitor will increase. |
| Display | LCD, with backlight with backlight showing gas type, gas concentration, alarm level status |
| Alarm | Alarm level 1: Visual alarm (red LED) Alarm level 2: Visual alarm (red LED) Alarm level 3: Visual and audible alarm (flashing white strobe LED and horn); Horn: 80 dB @ 1 m (3.3ft) |
| Warm-up time | 10 minutes |
| Sensing element technology gas | Non-dispersive infrared (NDIR) dual channel |
| Measuring range CO2 | 0 to 5000 ppm |
| Calibration | Non-interactive zero and span; Annual calibration required |
| Typical response time | <105 s (T90) |
| Measuring range temperature | -4 to 104 deg F (-20 to 40 deg C) |
| Agency Listing | ETL listed to UL 61010-1/-2-201, CSA C22.2#61010-1-12/-2-201; BTL listed to BTL-30001 |
| Pollution degree | 2 |
| Ambient humidity | 15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing |
| Ambient temperature | -4 to 122 deg F (-20 to 50 deg C) |
| Housing | UL94 5VA |
| Power rating under UL/CSA 61010-1 | 24 VAC only |
| Relay rating (UL/CSA tested) | SPDT, 5 A @ 125 VAC, non-inductive |
| Weight | 0.95 lb (0.43 kg) |