22G14-5B

SKU: 22G145B
$633.15

Call for Availability - (510) 636-7900

Details

Details

22G14-5B NO2 Gas Monitor, 2 Relays, 0 Analog Outputs, BACnet MS/TP

Detects harmful gas levels, typically in parking garages and mechanical rooms. 1 binary input; networks with other monitors over CAN bus and to the BAS over BACnet MS/TP.

Key Features

  • Enclosure: NEMA 2

Product Specifications

ManufacturerBelimo
Model22G145B (22G14-5B)
Measured valuesNO2
Number of relays2
Number of analog outputs0
Number of binary inputs1
CommunicationCAN bus, BACnet MS/TP
Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 20 to 25 V / DC 22 to 34 V
Power consumption AC5 VA
Power consumption DC3.7 W
Cable entry2 top, 2 bottom, 1 rear – 1/2" EMT Refer to remarks section
Cable specificationCommunication cable: 22 to 24 AWG (0.34 to 0.25 mm2) twisted shielded pair, jacketed, 17 pF/ft or less, 100 to 120 Ω impedance, stranded cable
FuseThermal PTC, auto-reset
CommunicationCAN bus BACnet MS/TP
MediumAir
Analog outputAnalog outputs: 2 to 10 V or 4 to 20 mA default
Relay outputSPDT, 5 A @ AC 240 V or 4 A @ DC 24 V, non- inductive, explosion proof, fail-safe (relay 1 only)
Mounting3 ft (1 m) above the floor to half of the ceiling height Refer to installation instructions
Coverage areaRadius: 50 ft (15 m) Area: 7500 ft2 (700 m2) There can be no obstructions such as walls, elevators, stairs, shelving with solid fill, tool chests, etc. Otherwise the time weighted average (TWA) for the gas to reach the monitor will increase.
DisplayLCD, with backlight showing gas type, gas concentration, alarm level status
AlarmAlarm level 1: Visual alarm (red LED) Alarm level 2: Visual alarm (red LED) Alarm level 3: Visual and audible alarm (flashing white strobe LED and horn) Horn: 80 dB @ 1 m (3.3ft)
Warm-up time5 minutes
Measured valuesNO₂
Sensing element technologyElectro-chemical
Measuring rangeNO₂: 0 to 10 ppm
AccuracyNO₂: 0 to 6.5% FS from 0 to 2 ppm @ 23.5 deg C (74 deg F) FS: Full scale of the measuring range
Measurement repeatability<+2% NO₂ equivalent same day
Long term stabilityNO₂: <2% per month
CalibrationNon-interactive zero and span Annual calibration required
Typical response time<30 s (T90)
Measuring range-4 to 122 deg F (-20 to 50 deg C) See the remarks section for more information about the temperature sensor
Degree of protection IEC/ENIP44
Degree of protection NEMA/ULNEMA 2
Agency ListingcULus listed to UL2075, ULC 588
Pollution degree2
Ambient humidity15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing
Ambient temperature-4 to 122 deg F (-20 to 50 deg C)
HousingUL94 5VA
Application notice for temperature sensorAll Belimo gas monitors and communication modules come with an internal temperature sensor. The purpose of this temperature sensor is to protect a space from overheating by activating alarm 1/relay 1. When using this feature, it is recommended to calibrate the temperature sensor to the ambient temperature (menu No. 50) after the gas monitor has been powered for 24 hours. For freeze protection, it is never recommended to set the temperature setpoint (menu setting No. 55) under 4 deg C (40 deg F).
Accuracy for gas monitorsCO and NO₂ sensor accuracies are not certified by UL. Both accuracies were internally tested and validated in an environmental chamber and compared to a high-accuracy reference device (analyzer).
Application notice for gas monitorsIntended applications include commercial and light industrial. Non-intended applications include heavy industrial and hazardous locations.