22G0214-5C

SKU: 22G02145C
$652.05

Call for Availability - (510) 636-7900

Details

Details

22G0214-5C CO and NO2 Gas Monitor, 0 Relays, 0 Analog Outputs

Detects harmful gas levels, typically in parking garages and mechanical rooms. 1 binary input; networks with other monitors over CAN bus.

Key Features

  • Enclosure: NEMA 2

Product Specifications

ManufacturerBelimo
Model22G02145C (22G0214-5C)
Measured valuesCO, NO2
Number of relays0
Number of analog outputs0
Number of binary inputs1
CommunicationCAN bus
Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 20 to 25 V / DC 22 to 34 V
Power consumption AC5 VA
Power consumption DC3.7 W
Cable entry2 top, 2 bottom, 1 rear – 1/2" EMT Refer to remarks section
Cable specificationCommunication cable: 22 to 24 AWG (0.34 to 0.25 mm2) twisted shielded pair, jacketed, 17 pF/ft or less, 100 to 120 Ω impedance, stranded cable
FuseThermal PTC, auto-reset
CommunicationCAN bus BACnet MS/TP
MediumAir
Analog outputAnalog outputs: 2 to 10 V or 4 to 20 mA default
Relay outputSPDT, 5 A @ AC 240 V or 4 A @ DC 24 V, non- inductive, explosion proof, fail-safe (relay 1 only)
Mounting3 ft (1 m) above the floor to half of the ceiling height Refer to installation instructions
Coverage areaRadius: 50 ft (15 m) Area: 7500 ft2 (700 m2) There can be no obstructions such as walls, elevators, stairs, shelving with solid fill, tool chests, etc. Otherwise the time weighted average (TWA) for the gas to reach the monitor will increase.
DisplayLCD, with backlight showing gas type, gas concentration, alarm level status
AlarmAlarm level 1: Visual alarm (red LED) Alarm level 2: Visual alarm (red LED) Alarm level 3: Visual and audible alarm (flashing white strobe LED and horn) Horn: 80 dB @ 1 m (3.3ft)
Warm-up time5 minutes
Measured valuesCO NO₂
Sensing element technologyElectro-chemical
Measuring rangeCO: 0 to 250 ppm NO₂: 0 to 10 ppm
AccuracyCO: +/-3% FS from 0 to 75 ppm @ 23.5 deg C (74 deg F) NO₂: 0 to 6.5% FS from 0 to 2 ppm @ 23.5 deg C (74 deg F) FS: Full scale of the measuring range
Measurement repeatability<+3% CO equivalent same day <+2% NO₂ equivalent same day
Long term stabilityCO: <5% per year NO₂: <2% per month
CalibrationNon-interactive zero and span Annual calibration required
Typical response time<30 s (T90)
Measuring range-4 to 122 deg F (-20 to 50 deg C) See the remarks section for more information about the temperature sensor
Degree of protection IEC/ENIP44
Degree of protection NEMA/ULNEMA 2
Agency ListingcULus listed to UL2075, ULC 588
Pollution degree2
Ambient humidity15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing
Ambient temperature-4 to 122 deg F (-20 to 50 deg C)
HousingUL94 5VA
This product can expose you to chemicals includuding lead, which is known to the State of
California to cause cancer and reproductive hararm. For more information go to
Terminal blocks can accommodate 1x 14...20 AWGG (2.5 to 0.5 mm2) or 2x 18 to 20 AWG
(0.75...0.5 mm2) copper cables in the same termrminal. Power cable size is recommended to be
Terminal blocks can accommodate 1x 14...20 AWGG (2.5 to 0.5 mm2) or 2x 18 to 20 AWG
(0.75...0.5 mm2) copper cables in the same termrminal. CAN bus and BACnet MS/TP
Cable entry1/2" EMT (UL certified with flexible metal duct). Maximum torque: 34 Nm (300 lb-in).