22G0214-5C
Details
Details
22G0214-5C CO and NO2 Gas Monitor, 0 Relays, 0 Analog Outputs
Detects harmful gas levels, typically in parking garages and mechanical rooms. 1 binary input; networks with other monitors over CAN bus.
Key Features
- Enclosure: NEMA 2
Product Specifications
| Manufacturer | Belimo |
|---|---|
| Model | 22G02145C (22G0214-5C) |
| Measured values | CO, NO2 |
| Number of relays | 0 |
| Number of analog outputs | 0 |
| Number of binary inputs | 1 |
| Communication | CAN bus |
| Nominal voltage | AC/DC 24 V |
| Nominal voltage frequency | 50/60 Hz |
| Nominal voltage range | AC 20 to 25 V / DC 22 to 34 V |
| Power consumption AC | 5 VA |
| Power consumption DC | 3.7 W |
| Cable entry | 2 top, 2 bottom, 1 rear – 1/2" EMT Refer to remarks section |
| Cable specification | Communication cable: 22 to 24 AWG (0.34 to 0.25 mm2) twisted shielded pair, jacketed, 17 pF/ft or less, 100 to 120 Ω impedance, stranded cable |
| Fuse | Thermal PTC, auto-reset |
| Communication | CAN bus BACnet MS/TP |
| Medium | Air |
| Analog output | Analog outputs: 2 to 10 V or 4 to 20 mA default |
| Relay output | SPDT, 5 A @ AC 240 V or 4 A @ DC 24 V, non- inductive, explosion proof, fail-safe (relay 1 only) |
| Mounting | 3 ft (1 m) above the floor to half of the ceiling height Refer to installation instructions |
| Coverage area | Radius: 50 ft (15 m) Area: 7500 ft2 (700 m2) There can be no obstructions such as walls, elevators, stairs, shelving with solid fill, tool chests, etc. Otherwise the time weighted average (TWA) for the gas to reach the monitor will increase. |
| Display | LCD, with backlight showing gas type, gas concentration, alarm level status |
| Alarm | Alarm level 1: Visual alarm (red LED) Alarm level 2: Visual alarm (red LED) Alarm level 3: Visual and audible alarm (flashing white strobe LED and horn) Horn: 80 dB @ 1 m (3.3ft) |
| Warm-up time | 5 minutes |
| Measured values | CO NO₂ |
| Sensing element technology | Electro-chemical |
| Measuring range | CO: 0 to 250 ppm NO₂: 0 to 10 ppm |
| Accuracy | CO: +/-3% FS from 0 to 75 ppm @ 23.5 deg C (74 deg F) NO₂: 0 to 6.5% FS from 0 to 2 ppm @ 23.5 deg C (74 deg F) FS: Full scale of the measuring range |
| Measurement repeatability | <+3% CO equivalent same day <+2% NO₂ equivalent same day |
| Long term stability | CO: <5% per year NO₂: <2% per month |
| Calibration | Non-interactive zero and span Annual calibration required |
| Typical response time | <30 s (T90) |
| Measuring range | -4 to 122 deg F (-20 to 50 deg C) See the remarks section for more information about the temperature sensor |
| Degree of protection IEC/EN | IP44 |
| Degree of protection NEMA/UL | NEMA 2 |
| Agency Listing | cULus listed to UL2075, ULC 588 |
| Pollution degree | 2 |
| Ambient humidity | 15 to 90% RH continuous, 0 to 99% RH intermittent, non-condensing |
| Ambient temperature | -4 to 122 deg F (-20 to 50 deg C) |
| Housing | UL94 5VA |
| This product can expose you to chemicals includ | uding lead, which is known to the State of |
| California to cause cancer and reproductive har | arm. For more information go to |
| Terminal blocks can accommodate 1x 14...20 AWG | G (2.5 to 0.5 mm2) or 2x 18 to 20 AWG |
| (0.75...0.5 mm2) copper cables in the same term | rminal. Power cable size is recommended to be |
| Terminal blocks can accommodate 1x 14...20 AWG | G (2.5 to 0.5 mm2) or 2x 18 to 20 AWG |
| (0.75...0.5 mm2) copper cables in the same term | rminal. CAN bus and BACnet MS/TP |
| Cable entry | 1/2" EMT (UL certified with flexible metal duct). Maximum torque: 34 Nm (300 lb-in). |