171A-10304
Details
Details
171A-10304 1/2 in. 2-Way Ball Valve with GDE131.1P Non-Spring Return Actuator, Floating, 24 VAC
Holds its last position on power loss (fail-in-place).
Runs on AC power only; no DC rating.
Has no position feedback or auxiliary switches.
Handles hot or chilled water up to 50% glycol, 0 to 250 deg F; not for steam.
Limits operating differential pressure to 60 psi.
Key Features
- Cv: 2.5
- Close-off: 200 psi
- Ball: chrome-plated brass; stem: brass
- Flow characteristic: equal percentage
- Torque: 44 lb-in
Product Specifications
| Manufacturer | Siemens |
|---|---|
| Model | 171A10304 (171A-10304) |
| Product | 599 Series 2-way ball valve + OpenAir GDE131.1P non-spring return actuator assembly |
| Valve body part number | 599-10304 |
| Fail action | Fail-in-place (non-spring return); holds position on power failure |
| Line size | 1/2 in (15 mm) |
| Cv (Kvs) | 2.5 (2.2) |
| Port | Characterized (flow characterizer insert) |
| Ball material | Chrome-plated brass |
| Stem material | Brass |
| Body material | Brass: ASTM B283, C37700 |
| Ball seals | Glass filled PTFE with EPDM O-rings |
| Flow characterizer material | Glass filled PTFE |
| End connections | Internal NPT |
| Stem seals | EPDM O-rings |
| Stem design | Blow-out proof stem withstands high pressure |
| Valve body rating | ANSI 250/600 WOG |
| Controlled medium | Water, water-glycol solutions to 50% |
| Angle of rotation | 0 to 90 deg |
| Flow characteristic | Equal percentage (characterized bodies; parabolic flow characterizer orifice) |
| Canadian Registration Number (CRN) | OC8213.5ADD4 |
| Mounting location | NEMA 1 (interior only); NEMA 3R (with weather shield) |
| Mounting plate | Universal mounting plate; actuator and plate can be rotated in 90-degree increments (any of four rotation angles relative to the valve body) |
| Thermal barrier | Standoffs provide a thermal barrier between the actuator and the mounting plate |
| Manual operation | Operating handle for manual operation |
| Orientation | Best performance with actuator above the valve body; in a horizontal pipe, any position between vertical and 90 deg; may also be installed vertically; do not install with the actuator below horizontal or upside-down |
| Service envelope | 2-1/2 in (60 mm); 8 in (200 mm) above; 1 in (25 mm) at sides; 4 in (100 mm) at end |
| Assembly wiring | When ordered as an assembly, the actuator is provided with 3-foot (.9 m) wires |
| Close-off rating | 200 psi (1379 kPa), ANSI Class IV |
| Maximum operating differential pressure | 60 psi (414 kPa) |
| Media temperature | 0 deg F to 250 deg F (-18 deg C to 121 deg C) |
| Dimension A (Length) | 2-7/16 (61) in |
| Dimension B (Height) | 2-1/4 (57) in |
| Dimension C (C Length, GDE (171A-D)) | 5-1/4 (133) in |
| Dimension C (C Length, GQD (171H, J, K, L, N)) | 5-1/4 (133) in |
| Dimension D (Width) | 2-3/4 (70) in |
| Dimension E (Height) | 4-13/16 (123) in |
| Valve and bracket weight | 1 lb (0.45 kg) |
| Assembly wiring | Actuator ships with 3 ft (0.9 m) wires when ordered as an assembly |
| Actuator | GDE131.1P, non-spring return (fail-in-place), floating, 24 VAC |
| Actuator type | OpenAir non-spring return, direct-coupled rotary electronic actuator, 24 VAC floating control |
| Operating voltage (G-Y1 or G-Y2) | 24 VAC +20%, -15% |
| Actuator frequency | 50/60 Hz |
| Power consumption | 2.3 VA |
| Actuator equipment rating | Class 2 according to UL, CSA; Class III per EN60730 |
| Control signal | Floating (tri-state): 24 VAC on wires 1 and 6 (G-Y1) rotates clockwise; 24 VAC on wires 1 and 7 (G-Y2) rotates counterclockwise; angle of rotation is proportional to how long the signal is applied |
| Wiring (pre-cabled leads) | 1 = Supply G (red); 6 = Y1 control signal clockwise (violet); 7 = Y2 control signal counterclockwise (orange) |
| Direction of rotation | Reversed by interchanging wires 6 and 7 (Y1 and Y2) at the controller |
| Position feedback | None (feedback potentiometer only on GDE132.1P; cannot be added in the field) |
| Auxiliary switches | None (dual auxiliary switches only on GDE136.1P; cannot be added in the field) |
| Actuator torque | 44 lb-in (5 Nm) |
| Running time (90 deg opening or closing) | 90 sec at 60 Hz (108 sec at 50 Hz) |
| Nominal angle of rotation | 90 deg |
| Maximum angular rotation | 95 deg |
| Action on power failure | Holds position on power failure or with no control voltage (non-spring return, fail-in-place) |
| Actuator manual override | Yes - red slide knob; move and lock position with no power present; returns to automatic control when power is restored |
| Mechanical range adjustment | Adjustable mechanical range stop (set screw, 4 mm hex) |
| Actuator enclosure | NEMA Type 2; IP54 according to EN 60529 |
| Outdoor rating | NEMA Type 4X (UL listed) only when installed with ASK75.7U weather shield and outdoor-rated conduit fittings |
| Actuator housing material | Durable plastic |
| Actuator gear lubrication | Silicone-free |
| Ambient temperature, operation | -25 deg F to 130 deg F (-32 deg C to 55 deg C) |
| Ambient temperature, storage and transport | -40 deg F to 158 deg F (-40 deg C to 70 deg C) |
| Ambient humidity | 95% rh (non-condensing) |
| Agency certification | UL listed to UL873; cUL certified to Canadian Standard C22.2 No. 24-93; CE certified |
| Plenum approval | Approved for installation in plenum areas by UL per UL 1995 |
| EMC conformity (plenum models) | EMC directive 2004/108/EC; emissions EN61000-6-3; immunity EN61000-6-2 |
| Actuator connection | Pre-cabled, 18 AWG |
| Standard cable length | 3 ft (0.9 m) |
| Actuator life cycle | Designed for over 60,000 full strokes and a minimum of 1.5 million repositions at rated torque and temperature |
| Actuator dimensions | 6.2 in L x 2.8 in W x 2.4 in D (157 mm L x 71 mm W x 61 mm D) |
| Actuator weight | 1.06 lb (0.48 kg) |
| Transformer requirements | Earth-ground isolating step-down Class 2 transformer; no autotransformers; total VA of all loads must not exceed transformer rating; recommended max 10 actuators per transformer |
| Controller time-out | Use a controller/software time-out that removes the drive signal after a predefined time to prolong actuator life |