101-78 Blocking Diode for 45UV5 Scanners Paralleled with Solid State Scanners
Connect in series with the signal lead (terminal 14) of a 45UV5 UV scanner whenever it is wired in parallel with a 45RM, 45FS or 45UVFS1 scanner; without it the solid state scanner can be damaged. Not required when both scanners are 45UV5 or neither is.
Key Features
- Use: in series with terminal 14 of the 45UV5
- Not required: two 45UV5 scanners, or two non-45UV5 types
Product Specifications
| Manufacturer | Fireye |
|---|---|
| Model | 10178 (101-78) |
| Type | Blocking diode |
| Use | In series with the signal lead (terminal 14) of a 45UV5 scanner wired in parallel with a 45RM1, 45RM2, 45RM4, 45FS1 or 45UVFS1 solid state scanner |
| Purpose | Prevents damage to the solid state scanner output circuit |
| Not required | Two 45UV5 scanners, or two scanners that are both non-45UV5 types |
| Shown in wiring for | 25SU5 controls, 25SU3-5166/-5168 control system, 192SU3 adapters for 25SU3-2100 |